| Plan Review Notes For Permit 17050701 |
| Permit Number |
17050701 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-05-23 16:27:41 | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70 2011 EDITION | | | | | | PAGE E0.3 | | | | | | NEED TO SHOW GROUNDING OF THE SERVICE FROM GUTTER | | | LOADS ON PANEL "H" SHOW 50 KVA FOR "LA", 10 KVA FOR | | | "LB" | | | LOADS ON PANELS SHOWN ARE 102.7 KVA FOR "LA", AND 33.5 | | | KVA FOR "LB" | | | | | | PLEASE SHOW DETAILED LOAD CALCULATION FOR "H" PANEL | | | | | | NEED FAULT CURRENT CALCULATION FOR THE NEW TRANSFORMERS | | | TA AND TC AND "H" | | | | | | PAGE E1.1 | | | | | | NO FIXTURES SHOWN IN HALF OF THE UNIT, NEED CUT SHEETS | | | ON FIXTURES IN ORDER TO CHECK | | | COMPLIANCE WITH POWER ALLOWNACES |
|