2017-05-19 10:55:312014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17050701
 ADD: 480 HIBISCUS ST. SUITE # 116
 CONT: FLORIDA DEVELOPMENT
 TEL: 954-707-1309
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. MAY 19, 2017
 ACTION: DENIED
  
 1) PLEASE PROVIDE DOCUMENTATION OF OWNERSHIP FOR THIS
 UNIT. THE CITY RECORD ARE DIFFERENT FROM THE PERMIT
 APPLICATION AND THE PALM BEACH COUNTY PROPERTY
 APPRAISERS OFFICE IS DIFFERENT FROM BOTH.
 PROVIDE DOCUMENTATION OF OWNERSHIP. 2014 FLORIDA
 BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 105.1PERMITS/ REQUIRED.
  
  
 2) BOTH SETS OF THE ARCHITECTURAL SHEETS ARE MISSING
 THE ARCHITECTS SIGNATURE, DATE AND SEALED PLANS.
 61 G 1-16.003 USES OF SEAL. EFFECTIVE 04/18/2000. THE
 PERSONAL SEAL, SIGNATURE AND DATE OF THE ARCHITECT
 SHALL APPEAR ON ALL ARCHITECTURAL DOCUMENTS TO BE FILED
 FOR PUBLIC RECORD.
  
 3) SHEET A210:
 3A) PLEASE NOTE THIS IS CONSIDERED A CHANGE IN
 OCCUPANCY, WILL NEED TO SHOW COMPLIANCE WITH 2014
 FBC-EXISTING BUILDING CODE CHAPTER 10, SECTION 1001.3.1
 PARTIAL CHANGE OF OCCUPANCY CLASSIFICATION.
 WHERE A PORTION OF AN EXISTING BUILDING IS CHANGED TO A
 NEW OCCUPANCY CLASSIFICATION, SECTION 1012 SHALL APPLY.
  
 3B) TYPE OF CONSTRUCTION IS LABELED III-B & ALLOWABLE
 HEIGHT OF 3 STORIES. PLEASE NOTE THIS TENANT SPACE IS
 LOCATED WITHIN A 10 STORY HIGH RISE, ON THE 2ND FLOOR
 AND ABOVE ALL UNITS BEING R2 OCCUPANCY. IN THE 2014
 FBC-B TABLE 503 INDICATES THIS BUILDING TO BE A MINIMUM
 BUILDING TYPE IB FOR 11 STORIES.
  
 3C) OCCUPANCY TYPE INDICATED FOR THE BAKERY IS A
 BUSINESS OCCUPANCY. THERE IS NO LIFE SAFETY PLAN
 PROVIDED. NOTED THERE IS A PROPOSED KITCHEN LAYOUT PLAN
 AND AN EQUIPMENT PLAN WITH PROPOSED FURNITURE LAYOUT
 WITH FURNITURE SCHEDULE, THE FURNITURE SCHEDULE HAS
 LEFT OUT THE BENCH SEATING AT THE MIRRORED WALL. WITH
 THE ADDITIONAL SEATING ALONE THE SEAT COUNT ALONE IS 56
 OCCUPANTS. WITH THIS OCCUPANT LOAD ALONE THIS TENANT
 SPACE IS AN A2 OCCUPANCY303.3.
  
 3D) PLEASE PROVIDE A LIFE SAFETY PLAN. 2014 FLORIDA
 BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT AISLES
 EXIT ACCESS
 EXITS
 EXIT DISCHARGE
 STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
  
 3E) WITH THE PLANS INDICATING A SEATING AREA OF 1,317
 SQ. FT. / 15= 88 OCCUPANTS A A2 OCCUPANCY, OVER 50
 OCCUPANTS AND AN SQUARE FOOT AREA OF 750 SQ. FT. FBC-B
 303.3.
  
 3F) SHEET A210 INDICATES THE DOORS AND DOOR SCHEDULE
 BUT DOES NOT INDICATE THE HARDWARE ON THE EXIT DOORS.
 PLEASE INDICATE COMPLIANCE WITH 2014 FBC-B 1008.1.10
 PANIC AND FIRE EXIT HARDWARE. PANIC HARDWARE REQUIRED
 WITH OCCUPANT LOAD OF 50 OR MORE.
  
 4) SHEET A211:
 4A) THIS SHEET SHOWS THE SEATING FLOOR PLAN BUT DOES
 NOT SHOW COMPLIANCE WITH THE 2014 FBC-ACCESSIBILITY
 CODE FOR;
  
 4A)(1) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE
 CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE
 SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902.
  
 4A)(2) 226.2 DISPERSION. DINING SURFACES AND WORK
 SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES. THIS WOULD ALSO INCLUDE
 EXTERIOR SEASONAL SEATING.
  
 4A)(3) 902.1 .DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, BOOTHS AND SEASONAL SEATING.
  
 4A)(4)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR
 FLOOR SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 4A)(4)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND
 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 4B) EXIT PLEASE IDENTIFY WHICH DOORS ARE ACCESSIBLE
 EXITS (2) REQUIRED > THAN 50,
 ACCESS. CODE 06.4.1 PUBLIC ENTRANCES. IN ADDITION TO
 ENTRANCES REQUIRED BY 206.4.2 THROUGH 206.4.9,
 AT LEAST 60 PERCENT OF ALL PUBLIC ENTRANCES SHALL
 COMPLY WITH 404.(MINIMUM OF 2 ENTRANCES).
  
 4C) IN THE ORIGINAL BUILDING DESIGN THE STAIRS TO THE
 MEZZANINE WENT UP TO A MID-LANDING AND RETURNED ON
 THEMSELVES. THE PLANS ARE SILENT IF THESE ARE A NEW
 STAIRCASE TO THE MEZZANINE LEVEL? 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 5) SHEET A401 DOES NOT PROVIDE ANY DETAILS FOR REQUIRED
 ACCESSIBLE SIGNAGE. SEE ACCESSIBILITY CODE:
 5A) 703.1 SIGNS SHALL COMPLY WITH 703. WHERE BOTH
 VISUAL AND TACTILE CHARACTERS ARE REQUIRED, EITHER ONE
 SIGN WITH BOTH VISUAL AND TACTILE CHARACTERS, OR TWO
 SEPARATE SIGNS, ONE WITH VISUAL, AND ONE WITH TACTILE
 CHARACTERS, SHALL BE PROVIDED.
  
 5B) 703.4.1 HEIGHT ABOVE FINISH FLOOR OR GROUND.
 TACTILE CHARACTERS ON SIGNS SHALL BE LOCATED 48 INCHES
 MINIMUM ABOVE THE FINISH FLOOR OR GROUND SURFACE,
 MEASURED FROM THE BASELINE OF THE LOWEST TACTILE
 CHARACTER AND 60 INCHES MAXIMUM ABOVE THE FINISH FLOOR
 OR GROUND SURFACE, MEASURED FROM THE BASELINE OF THE
 HIGHEST TACTILE CHARACTER.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.