| 2017-05-30 13:29:24 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET E 1 - THERE ARE INCORRECT EDITIONS DATES |
| | REFERENCES TO THE FIRE CODES INDICATED. |
| | |
| | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| | 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING |
| | THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| | APPLICABLE CODES OR STANDARDS. |
| | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 13, 2010 EDITION. |
| | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 72, 2010 EDITION. |
| | ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION. |
| | |
| | |
| | |
| | 2) SHEET E 1 - THIS INSTALLATION APPEARS TO FUNCTION AS |
| | THE BACKUP TO THE LIFE SAFETY SYSTEMS. |
| | |
| | EMERGENCY AND STANDBY POWER SYSTEMS SHALL COMPLY WITH |
| | NFPA 110, 2013 EDITION. |
| | |
| | PLEASE ENSURE COMPLIANCE AND PROVIDE AN APPLICABLE |
| | NOTE. |
| | |
| | |
| | |
| | 3) THE SCOPE OF WORK DOES NOT ADDRESS HOW LONG THE |
| | INSTALLTION WILL TAKE AND/OR FOR PROVIDING APPLICABLE |
| | ASSURANCES OF MAINTAINING THE EXISTING LIFE SAFETY |
| | PROTECTION. |
| | |
| | PLEASE PROVIDE. |
| | |
| | |
| | |
| | 4) ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE |
| | DONE UNDER SEPARATE SHOP DRAWING BY CERTIFIED LIFE |
| | SAFETY CONTRACTORS. |
| | |
| | PLEASE PROVIDE AN APPLICABLE NOTE. |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |