| 2017-05-31 16:09:57 | BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 17050689 |
| | W. P. B. PERMIT: 15031312 |
| | ADD: 333 FERN ST. |
| | CONT: KAST CONSTRUCTION |
| | CONTACT :ROB HALL |
| | TEL: (561)689-2910 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2ND REVIEW |
| | DATE: WED. MAY 31/ 2017 |
| | ACTION: DENIED |
| | |
| | |
| | |
| | 1A)SEMI COMPLIED. THE COVERSHEET BREAK METAL AT ENTRY |
| | CLADDING CALCULATIONS SUBMITTAL, DOES HAVE A TABLE OF |
| | CONTENTS THE SEAL IS PRINTED BUT THE SIGNATURE IS |
| | DIGITAL, THE EDGES OF THE SIGNATURE IS PIXALATED. |
| | 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR INDEX |
| | SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED AND |
| | THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE |
| | PRODUCTION & PREPARATION OF EACH SECTION OF THE |
| | ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION |
| | ON THE COVER SHEET OR INDEX LISTING HOW MANY PAGES ARE |
| | COVERED UNDER THE COVER SHEET OR INDEX SHEET. |
| | |
| | 1B) PAST THE FIRST 10 PAGES THAT IS COVERED UNDER THE |
| | INDEX SHEET THERE ARE 5 ADDITIONAL SHEETS LISTED 1-5 |
| | WITH A MINITURIZED SEAL 1 1/4 INCHES IN DIAMETER. AGAIN |
| | THE SIGNATURE IS COPIED. |
| | 61G15-23.001 ENGINEERS SEALS ACCEPTABLE TO THE BOARD. |
| | SAID SEAL SHALL BE A MINIMUM OF 1 7/8 INCHES IN |
| | DIAMETER, TO SAY LICENSE NOT CERTIFICATE. ALL ENGINEERS |
| | MUST BE UTILIZING SAID SEAL NO LATER THAN JANUARY 1, |
| | 2006. |
| | |
| | FL ADMIN CODE 61G15-23.002 ENGINEERS. EFFECTIVE DATE |
| | 05/06/2009. (2)(A) EVERY SHEET OF PLANS AND PRINTS |
| | WHICH MUST BE SEALED UNDER THE PROVISIONS OF CHAPTER |
| | 471, F.S., SHALL BE SEALED, SIGNED AND DATED BY THE |
| | PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE. |
| | |
| | 1) 1ST ROUND COMMENT. THE BREAK METAL AT ENTRY CLADDING |
| | CALCULATIONS SUBMITTAL, THE COVER PAGE SIGNED AND |
| | SEALED BY EVAN KENNEDY DOES NOT INCLUDE HOW MANY PAGES |
| | ARE COVERED UNDER THIS SEAL. WITHIN THE REPORT ARE |
| | MARKED PAGES 1-5 WITH A COPIED AND MINIATURIZED |
| | SIGNATURE AND SEAL. |
| | |
| | 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR INDEX |
| | SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED AND |
| | THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE |
| | PRODUCTION & PREPARATION OF EACH SECTION OF THE |
| | ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION |
| | ON THE COVER SHEET OR INDEX LISTING HOW MANY PAGES ARE |
| | COVERED UNDER THE COVER SHEET OR INDEX SHEET. . |
| | 61G15-23.001 ENGINEERS SEALS ACCEPTABLE TO THE BOARD. |
| | SAID SEAL SHALL BE A MINIMUM OF 1 7/8 INCHES IN |
| | DIAMETER, TO SAY LICENSE NOT CERTIFICATE. ALL ENGINEERS |
| | MUST BE UTILIZING SAID SEAL NO LATER THAN JANUARY 1, |
| | 2006. |
| | |
| | 2) COMPLIED. |
| | |
| | 3) COMPLIED. NOA 14-0811.20 REYNOBOND COMPOSITE WALL |
| | PANEL SYSTEM.ACM PANELS ARE AVAILABLE IN 3MM, 4MM AND |
| | 6MM THICKNESSES IN EITHER A STANDARD POLYETHYLENE (PE) |
| | OR FIRE RESISTANT (FR) CORE. |
| | |
| | 4) COMPLIED. 2010 FBC-B 1407.11.1- 1407.11. SEE NOA |
| | 14-0811.20 |
| | |
| | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |