| 2017-05-18 08:50:55 | BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 17041119 |
| | W. P. B. PERMIT: 15031312 |
| | ADD: 333 FERN ST. |
| | CONT: KAST CONSTRUCTION |
| | CONTACT :ROB HILL |
| | TEL: (561)689-2910 |
| | E-MAIL: [email protected] |
| | |
| | 1) THE BREAK METAL AT ENTRY CLADDING CALCULATIONS |
| | SUBMITTAL, THE COVER PAGE SIGNED AND SEALED BY EVAN |
| | KENNEDY DOES NOT INCLUDE HOW MANY PAGES ARE COVERED |
| | UNDER THIS SEAL. WITHIN THE REPORT ARE MARKED PAGES 1-5 |
| | WITH A COPIED AND MINIATURIZED SIGNATURE AND SEAL. |
| | |
| | 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR INDEX |
| | SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED AND |
| | THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE |
| | PRODUCTION & PREPARATION OF EACH SECTION OF THE |
| | ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION |
| | ON THE COVER SHEET OR INDEX LISTING HOW MANY PAGES ARE |
| | COVERED UNDER THE COVER SHEET OR INDEX SHEET. . |
| | 61G15-23.001 ENGINEERS SEALS ACCEPTABLE TO THE BOARD. |
| | SAID SEAL SHALL BE A MINIMUM OF 1 7/8 INCHES IN |
| | DIAMETER, TO SAY LICENSE NOT CERTIFICATE. ALL ENGINEERS |
| | MUST BE UTILIZING SAID SEAL NO LATER THAN JANUARY 1, |
| | 2006. |
| | |
| | 2) WIND CALCULATIONS ARE BASED ON ASCE 7-10 LOW RISE |
| | BUILDINGS (H<60 FT.) PLEASE NOTE NEGATIVE PRESSURES ARE |
| | TAKEN FROM THE ROOF LEVEL. NEGATIVE PRESSURES(Z), |
| | POSITIVE PRESSURES( H). ASCE 7-10. |
| | THIS IS A 16 STORY HIGH-RISE. ELEVATION TAKEN @ 15 |
| | FEET. CALCULATIONS NOT SHOWN ONLY THE END VALUES. |
| | |
| | 3) ACM PANELS ARE AVAILABLE IN 3MM, 4MM AND 6MM |
| | THICKNESSES IN EITHER A STANDARD POLYETHYLENE (PE) OR |
| | FIRE RESISTANT (FR) CORE. NO PRODUCT INFORMATION HAS |
| | BEEN SUBMITTED. 2010 FBC-B 1609.1.2 PROTECTION OF |
| | OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA |
| | DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE |
| | 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY |
| | OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| | PRODUCT APPROVALS: |
| | (31)(C) PANEL WALLS: ACM PANELS AND OTHER PRODUCTS |
| | INTRODUCED BY NEW TECHNOLOGIES |
| | |
| | 4) PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B 1407.11.1- |
| | 1407.11. |
| | |
| | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |