Plan Review Notes
Plan Review Notes For Permit 17050687
Permit Number 17050687
Review Stop G
Sequence Number 2
Notes
Date Text
2017-06-05 13:03:111) THE SUBMITTED FLOOR PLAN FOR THE GAS IS ILLEGIBLE.
 SUBMIT A CLEAR, EXPANDED FLOOR PLAN THAT REFLECTS THE
 SCOPE OF WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
 2) ONE EDGE OF THE GAS PIPE SCHEMATIC IS CUT OFF AND
 CANNOT BE READ.SUBMIT A COMPLETE PIPE SCHEMATIC FOR
 REVIEW. WPB AMEND. TO FBC SEC. 107.2.1.
 3) SHOW ALL THE CORRESPONDING EHD NUMBERS OF THE
 CORRUGATED STAINLESS STEEL TUBING FOR EACH PIPE SIZE.
 WPB AMENDMENTS TO FBC SEC.107.2.1, 2014 FBC-FUEL GAS
 TABLES 402.4. (15) THROUGH 402.4 (17).
 4 ) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2014 FBC-FUEL GAS
 SECS.401.8 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4
 (37) OR 2014 FBC-RES. SEC. G2413. REFER TO GAS PIPE
 SCHEMATIC WHERE THE EDGE IS CUT OFF.
 5) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER ) TO THE MOST REMOTE OUTLET IN THE BUILDING AND /
 OR SYSTEM PER THE 2014 FBC-FUEL GAS SEC.402.4.1 OR 2014
 FBC-RES. SEC. G 2413.3.
 6) SUBMIT TWO COPIES OF THE SIZING TABLES USED IN THE
 DESIGN FOR THIS GAS SYSTEM OR PLACE A NOTE ON BOTH SETS
 OF PLANS LISTING THE SIZING TABLES FROM THE GAS CODE OR
 OTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS
 SYSTEM. FGC SEC.402.3, FBCR SEC. G 2413.3.
 7) THE PIPING SCHEMATIC INDICATES A 2 LB. SYSTEM. SHOW
 THE LOCATION OF ALL STEP DOWN REGULATORS AND HOW THEY
 ARE BEING VENTED. SUBMIT MANUF. SPECS FOR THE
 REGULATORS.2014 FGC SEC.410.3, 410.1.
 8) A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR. 2014 FGC
 SEC.409.4.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  