| 2017-06-05 13:03:11 | 1) THE SUBMITTED FLOOR PLAN FOR THE GAS IS ILLEGIBLE. |
| | SUBMIT A CLEAR, EXPANDED FLOOR PLAN THAT REFLECTS THE |
| | SCOPE OF WORK TO BE DONE. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 2) ONE EDGE OF THE GAS PIPE SCHEMATIC IS CUT OFF AND |
| | CANNOT BE READ.SUBMIT A COMPLETE PIPE SCHEMATIC FOR |
| | REVIEW. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 3) SHOW ALL THE CORRESPONDING EHD NUMBERS OF THE |
| | CORRUGATED STAINLESS STEEL TUBING FOR EACH PIPE SIZE. |
| | WPB AMENDMENTS TO FBC SEC.107.2.1, 2014 FBC-FUEL GAS |
| | TABLES 402.4. (15) THROUGH 402.4 (17). |
| | 4 ) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| | BTU LOAD ON THE SYSTEM. REFER TO THE 2014 FBC-FUEL GAS |
| | SECS.401.8 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4 |
| | (37) OR 2014 FBC-RES. SEC. G2413. REFER TO GAS PIPE |
| | SCHEMATIC WHERE THE EDGE IS CUT OFF. |
| | 5) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| | METER ) TO THE MOST REMOTE OUTLET IN THE BUILDING AND / |
| | OR SYSTEM PER THE 2014 FBC-FUEL GAS SEC.402.4.1 OR 2014 |
| | FBC-RES. SEC. G 2413.3. |
| | 6) SUBMIT TWO COPIES OF THE SIZING TABLES USED IN THE |
| | DESIGN FOR THIS GAS SYSTEM OR PLACE A NOTE ON BOTH SETS |
| | OF PLANS LISTING THE SIZING TABLES FROM THE GAS CODE OR |
| | OTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS |
| | SYSTEM. FGC SEC.402.3, FBCR SEC. G 2413.3. |
| | 7) THE PIPING SCHEMATIC INDICATES A 2 LB. SYSTEM. SHOW |
| | THE LOCATION OF ALL STEP DOWN REGULATORS AND HOW THEY |
| | ARE BEING VENTED. SUBMIT MANUF. SPECS FOR THE |
| | REGULATORS.2014 FGC SEC.410.3, 410.1. |
| | 8) A LISTED SHUTOFF VALVE SHALL BE INSTALLED |
| | IMMEDIATELY AHEAD OF EACH MP REGULATOR. 2014 FGC |
| | SEC.409.4. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |