2017-05-17 05:05:481) SHOW ALL THE TYPES OF PIPE MATERIAL BEING INSTALLED,
 ALL PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING FOR EACH PIPE SIZE.
 WPB AMENDMENTS TO FBC SEC.107.2.1.
 2)LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU
 LOAD ON THE SYSTEM. REFER TO THE 2014 FBC-FUEL GAS
 SECS.401.8 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4
 (37) OR 2014 FBC-RES. SEC. G2413. THE BTU LOAD OF
 10,300 TO 180,000 FOR THE TANKLESS WATER HEATER IS
 UNACCEPTABLE. THE CORRECT PIPE SIZE CANNOT BE
 DETERMINED IF THE EXACT BTU LOAD IS NOT KNOWN.
 3) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER ) TO THE MOST REMOTE OUTLET IN THE BUILDING AND /
 OR SYSTEM PER THE 2014 FBC-FUEL GAS SEC.402.4.1 OR 2014
 FBC-RES. SEC. G 2413.3.
 4) ALL GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 SPEC SHEET FOR THE STOVE DOES NOT SHOW THAT IT IS
 LISTED AND LABELED. 2014 FBC-RESIDENTIAL SEC.G2404.3.
 5) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 OF ANY OPERABLE DOORS OR WINDOWS. THE LOCATION OF THE
 WATER HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMEND. TO FBC SEC. 107.2.1.
 6) SUBMIT TWO COPIES OF THE SIZING TABLES USED IN THE
 DESIGN FOR THIS GAS SYSTEM OR PLACE A NOTE ON BOTH SETS
 OF PLANS LISTING THE SIZING TABLES FROM THE GAS CODE OR
 OTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS
 SYSTEM. FGC SEC.402.3, FBCR SEC. G 2413.3.
 7) SUBMIT TWO COPIES OF ALL DOCUMENTS. ONLY ONE SET HAS
 BEEN SUBMITTED. WPB AMEND. TO FBC SEC. 107.2.1.
  