| 2017-05-17 13:45:49 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THE SUBMITTED PLANS SHEETS APPEARS TO BE RELATED TO |
| | GENERAL CIVIL PLANS WITH BLUE INK WRITING TO MOVE A |
| | FIRE HYDRANT 20' SOUTH. |
| | |
| | PLEASE PROVIDE GREATER DETAIL OF THE PROPOSED CHANGE |
| | AND THE EXACT LOCATION OF THE PROPOSED FIRE HYDRANT |
| | LOCATION. |
| | |
| | |
| | |
| | 2) THE THREE INDIVIDUAL PLAN SHEETS ARE LOOSE, |
| | DISORGANIZED AND NOT COMBINED TOGETHER. |
| | |
| | PLEASE ORGAINZE THEM AND BIND THEM TOGETHER. |
| | |
| | |
| | 3) THERE IS NO DOCUMENTATION THAT THE CONTRACTOR IS |
| | CERTIFIED TO DO PRIVATE UNDERGROUND FIRE LINE PER FL |
| | STATUTE. A RECORDS SEARCH UNDER THE CONTACTOR NMAE |
| | PROVIDED AND THE COMPANY NMAE COULD NOT BE LOCATED IN |
| | THE STATE DATABASE. |
| | |
| | PLEASE PROVIDE APPLICABLE AND REQUIRED LICENSING |
| | DOUMENTATION FOR UNDERGROUND FIRE LINE WORK. |
| | |
| | |
| | |
| | 4) THERE ARE NO MANUFACTURES EQUIPMENT OR MATERIALS |
| | SPECIFICATION SHEETS. |
| | |
| | PLEASE PROVIDE SPECIFICATION SHEETS FOR WHAT EQUIPMENT |
| | IS BEING PROPOSED TO BE INSTALLED. |
| | |
| | |
| | |
| | 5) THERE ARE NO INDICATIONS OF WHAT SIZE PIPE IS BEING |
| | USED. |
| | |
| | PLEASE PROVIDE. |
| | |
| | |
| | |
| | 6) THERE ARE NO FIRE CODE REFERENCES INDICATED FOR CODE |
| | COMPLAINCE. |
| | |
| | THE INSTALLATION SHALL BE INSTALLED AND TESTED WITHIN |
| | THE REQUIREMENTS OF NFPA 24, INSTALLATION OF PRIVATE |
| | FIRE SERVICE MAINS AND THEIR APPURTENANCES. |
| | |
| | PLEASE PROVIDE AND APPLICABLE NOTE AND ENSURE |
| | COMPLIANCE. |
| | |
| | |
| | |
| | |
| | |
| | 7) THE INSTALLATION SHALL BE INSPECTED BY A WEST PALM |
| | BEACH FIRE INSPECTOR PRIOR TO ANY COVE-ROVER OF |
| | EQUIPMENT. |
| | |
| | |
| | |
| | 8) THE SUBMITTED SHEETS HAVE A COPY OF AN ENGINEER |
| | STAMP DATED JUNE 14, 2006. |
| | |
| | IS THIS ENGINEER TAKING RESPONSIBILITY FOR THIS |
| | INSTALLATION? |
| | |
| | |
| | |
| | 9) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 10) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |