| 2017-06-16 10:55:00 | 2ND REVIEW |
| | |
| | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | NEW COMMENT: |
| | |
| | 1) THE SUBMITTED PLANS INDICATES WORK FOR THE STAIRS |
| | AND RAMPS ONLY, WITH THE TRAILERS INDICATED AS "BY |
| | OTHERS". THE APPLICATION STATES "ALL WE ARE DOING IS |
| | MOVING THE PREVIOUSLY PERMITTED TEMP CLUBHOUSE TO NEW |
| | LOCATION." |
| | |
| | IS THIS PERMIT JUST FOR THE STAIRS AND RAMPS, OR IS IT |
| | FOR THE ENTIRE PROJECT, INCLUDING THE TRAILER |
| | RELOCATION AND OCCUPANCY? |
| | |
| | IF AN APPROVED PERMIT EXISTS THEN A REVISION MAY NEED |
| | TO BE SUBMITTED TO SHOW CHANGES.WAS THAT PERMIT EVER |
| | CO'D? WAS THAT BUILDING EVER OCCUPOED? ARE THE EXISTING |
| | STAIRS BEING MOVED? ETC. |
| | |
| | PLEASE ADDRESS AND CLARIFY |
| | |
| | |
| | |
| | PREVIOUS COMMENTS: |
| | |
| | |
| | 1) THE APPLICATION INDICATES A RELOCATION OF TRAILER. |
| | THERE IS NO INDICATION OF THE PLAN OF THE ORIGINAL |
| | LOCATION. |
| | |
| | PLEASE INDICATE. |
| | |
| | 1A.) NOT ADDRESSED, FAILED. |
| | |
| | PLEASE SHOW PREVIOUS LOCATION IN RELATION TO NEW |
| | LOCATION. |
| | |
| | |
| | |
| | 2) CONFIRMED |
| | |
| | |
| | |
| | 3) THE FLOOR PLAN INDICATE OFFICE SPACES, EVEN IN THE |
| | CENTRAL OPEN AREA. SHEET A001 INDICATES PRO SHOP; |
| | MERCANTILE. |
| | |
| | IS THIS AN OFFICE TRAILER OR A PRO SHOP, MIXED |
| | OCCUPANCY OR SEPARATED? |
| | |
| | PLEASE PROVIDE THE APPLICABLE OCCUPANCY PER NFPA 101, |
| | 5TH EDITION, CHAPTER 6, OCCUPANCY CLASSIFICATION AND |
| | ENSURE COMPLIANCE. |
| | |
| | 3A) NOT ADDRESSED, FAILED. IS THIS PERMIT JUST FOR THE |
| | STAIRS AND RAMPS? |
| | |
| | |
| | |
| | |
| | 4) ON REVIEW OF THE SUBMITTAL, NFPA 241 HAS BEEN |
| | REVIEWED. THESE TRAILERS ARE USED FOR THE TEMPORAY USE |
| | OF BUILDINGS UNDER CONSTRUCTION. |
| | |
| | THE CONFIGURATION OF THREE TRAILERS TOGETHER |
| | CONSTITUTIES AS A COMPLEX AND NEEDS TO BE PROTECTED |
| | ACCORDINGLY. |
| | |
| | CHAPTER 4 TEMPORARY CONSTRUCTION, EQUIPMENT, AND |
| | STORAGE |
| | |
| | 4.1 APPLICATION. FOR THE PURPOSES OF CHAPTER 4, THE |
| | TERM TEMPORARY SHALL BE DEFINED AS THE DURATION OF THE |
| | CONSTRUCTION PROJECT. |
| | 4.2 TEMPORARY OFFICES AND SHEDS. |
| | 4.2.1* SEPARATION DISTANCES BETWEEN BUILDINGS UNDER |
| | CONSTRUCTION AND CONSTRUCTION-RELATED STRUCTURES, SUCH |
| | AS TEMPORARY OFFICES, TRAILERS, SHEDS, AND OTHER |
| | FACILITIES FOR THE STORAGE OF TOOLS AND MATERIALS |
| | HAVING COMBUSTIBLE CONSTRUCTION OR CONTENTS, SHALL BE |
| | IN ACCORDANCE WITH TABLE 4.2.1. |
| | |
| | 4.2.2* DETACHMENT BETWEEN TEMPORARY STRUCTURES, |
| | ADEQUATE TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND |
| | PORTABLE EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE |
| | AUTHORITY HAVING JURISDICTION. |
| | |
| | A.4.2.2 WHERE LOCATED 9M(30 FT) OR MORE FROM THE |
| | STRUCTURE AND CONSTRUCTED OF COMBUSTIBLE MATERIALS, IT |
| | IS RECOMMENDED THAT TEMPORARY SUPPORT BUILDINGS BE |
| | DIVIDED INTO SMALL, DETACHED UNITS TO MINIMIZE FIRE |
| | LOSS. LARGE CONSTRUCTION SUPPORT |
| | COMPLEXES SHOULD BE PROTECTED WITH ADEQUATE FIRE |
| | PROTECTION (E.G., AUTOMATIC SPRINKLERS, YARD HYDRANTS, |
| | HOSE, AND EXTINGUISHERS) AS REQUIRED BY THE AUTHORITY |
| | HAVING JURISDICTION. |
| | |
| | |
| | TEMPORARY FIRE SPRINKLER PROTECTION IS REQUIRED WITHIN |
| | THESE TRAILERS. A 13D SYSTEM CAN BE CONSIDERED IN LEIU |
| | OF NFPA 13 SYSTEM, BASED ON AN EOR REVIEW AND |
| | SUBMITTAL. |
| | |
| | AN ALTERNATIVE COMPREHENSIVE LIFE SAFETY SYSTEMS |
| | EQUIPMENT INSTALLATION AND WATER SUPPLY REVIEW MAY BE |
| | CONSIDERED. |
| | |
| | PLEASE ADDRESS. |
| | |
| | |
| | 4A) NOT ADDRESSED, FAILED |
| | |
| | DIMENSIONS TO ALL EXISTING BUILDINGS AND PROPOSED |
| | BUILDINGS SHALL BE CLEARLY INDICATED. |
| | |
| | DIMENSION TO THE TWO NEAREST FIRE HYDRANTS SHALL BE |
| | INDICATED. |
| | |
| | |
| | |
| | 5) PLEASE CONTACT/COORDINATE WITH THE OFFICE OF THE |
| | FIRE MARSHAL TO DISCUSS AND/OR CONFIRM INSTALLATION |
| | WITH FORTHCOMING SHOP DRAWINGS. |
| | |
| | PLEASE CLARIFY OR PROVIDE A NOTE OF FIRE SPRINKLER |
| | INSTALLATION. |
| | |
| | |
| | 5A) NOT ADDRESSED, FAILED. |
| | |
| | PLEASE CLARIFY OR PROVIDE A NOTE OF FIRE SPRINKLER |
| | INSTALLATION. |
| | |
| | |
| | |
| | |
| | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | 6A) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | 7A) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |