Plan Review Notes
Plan Review Notes For Permit 17050665
Permit Number 17050665
Review Stop B
Sequence Number 1
Notes
Date Text
2017-05-31 10:41:32****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. SCOPE NOT CLEAR.
  
 ON THE PERMIT APPLICATION: DESCRIPTION IS FOR A
 TEMPORARY CLUBHOUSE IN THE DESCRIPTION
 ON THE PERMIT APPLICATION: PROJECT NAME IS "TEMPORARY
 SALES TRAILER"
 SITE PLAN HAS "CLUBHOUSE" HIGHLIGHTED
 ARCHITECT'S LETTER AND PLAN REFERS TO "MODULAR PRO
 SHOP" (STOFFT)
 MODULAR PLANS ARE FOR OFFICES
  
 PLEASE CORRELATE. A COMPLETE REVIEW CANNOT BE DONE AT
 THIS TIME. FOR THIS REVIEW, THIS IS BEING REVIEWED AS A
 DCA MANUFACTURED BUILDING RELOCATION, CHANGE OF
 OCCUPANCY. PLANS SHOULD BE REVISED TO CLEARLY REFLECT
 THIS OR, IF THIS IS NOT THE CASE, REVISE TO CLARIFY
 SCOPE FBC 107.
  
 2. MODULAR BUILDING IS FOR OFFICES AND BUSINESS
 OCCUPANCY (MODSPACE). SHEET A101 (STOFFT) DECLARES
 BUSINESS OCCUPANCY BUT CALLS THIS A "PRO SHOP" WHICH
 APPEARS TO BE MERCANTILE, FBC B 309. ARCHITECT USES 100
 SF PER PERSON, MERCANTILE REQUIRES 30 SF PER PERSON FBC
 B 1004.1.2.
  
 OTHER PLACES CALL THIS A "CLUBHOUSE" WHICH IS ASSEMBLY
 (FBC B 303.1) WITH A HIGHER OCCUPANT LOAD.
  
 IF ARCHITECT DOES NOT AGREE THAT THE PROPOSED "PRO
 SHOP" IS MERCANTILE, REVISE THE PLAN TO INCORPORATE
 PROPOSED USE TO CLARIFY WHY THE PRO SHOP IS BUSINESS
 OCCUPANCY.
  
 A COMPLETE REVIEW CANNOT BE DONE AT THIS TIME DUE TO
 INCONSISTENT INFORMATION. REVISE ALL PLANS TO BE
 CONSISTENT.
  
 3. MODSPACE PLANS CALL THIS A "MODULAR", PROVIDE DCA
 APPROVAL (LETTER SHOWING APPROVAL NUMBER AND PLANS). IF
 THIS IS A DCA MANUFACTURED BUILDING, AND IT WAS
 DESIGNED TO BUSINESS OCCUPANCY, AND NOW MIXED OCCUPANCY
 (BUSINESS & MERCANTILE) IS PROPOSED, A CHANGE OF
 OCCUPANCY IS REQUIRED.
  
 MECHANICAL AND PLUMBING ARE NOT BEING REVIEWED AT THIS
 TIME AS OCCUPANCY AND PROPOSED USE IS NOT CLEAR.
  
 PER DCA, AN EXISTING MODULAR BUILDING BEING CONVERTED
 FROM ONE OCCUPANCY TYPE TO ANOTHER REQUIRES THAT THE
 BUILDING BE BROUGHT INTO COMPLIANCE WITH THE CURRENT
 FBC. MECHANICAL AND PLUMBING WILL BE REVIEWED AFTER
 SCOPE IS CLARIFIED AND PLANS ARE MADE CONSISTENT.
  
 HTTP://WWW.FLORIDABUILDING.ORG/FBC/MANUFACTURED_BUILDIN
 GS/Q_&_A_0208_V3.PDF
  
 THE DCA APPROVAL SHOULD BE PROVIDED TO DOCUMENT
 COMPLIANCE FOR EXISTING MODULAR STRUCTURE. PLANS SHOULD
 SHOW COMPLIANCE FOR THE CHANGE OF OCCUPANCY, ALL
 TRADES.
  
 4. SHEET C1 (MODSPACE) HAS NOTES REGARDING THE INITIAL
 CONSTRUCTION UNDER FBC 2010, BUT ALSO DECLARES FBC 2014
 UNDER "STRUCTURAL LOAD LIMITATIONS". A NOTE STATES THAT
 THIS WAS DESIGNED IN COMPLIANCE WITH ACI318, AISC,
 ACI530. PLEASE REMOVE STANDARDS NOT APPLICABLE TO THIS
 STRUCTURE, FBC 107.
  
 5. ONE ACCESSIBLE RAMP IS SHOWN, THREE ENTRANCES/EXITS
 ARE SHOWN. FBC A 206.4.1, IT APPEARS THAT TWO ARE
 REQUIRED (NOTE DEFINITION OF "PUBLIC ENTRANCE" INCLUDES
 ALL ENTRANCES THAT ARE NOT SERVICE OR RESTRICTED
 ENTRANCES), REVISE PLAN TO INCLUDE 2ND ACCESSIBLE
 ENTRANCE.
  
 6. A001, REMOVE NOTES NOT APPLICABLE OR REVISE TO BE
 APPLICABLE; FOR INSTANCE, CLIMATE NOTE REFERS TO FBC
 RESIDENTIAL CODE, FBC 107, ALSO OTHER PLACES REFER TO
 FBC R. A101 HAS A NOTE REGARDING "FBC 2010
 ACCESSIBILITY CODE, CHAPTER 11". REMOVE NOTES NOT
 APPLICABLE TO THIS JOB, REVISE NOTES WHICH ARE REQUIRED
 TO DEMONSTRATE CODE COMPLIANCE. DUE TO THE NATURE OF
 THIS JOB, IT APPEARS THAT MANY (POSSIBLY MOST) SHOULD
 BE REMOVED OR REVISED.
  
 7. IF THIS IS A MODIFICATION OF AN EXISTING DCA
 MODULAR, REVISE MODSPACE NOTES TO INCLUDE THE FOLLOWING
 INFORMATION FBC 107:
  
 MODSPACE PLAN SHEET A1 SHOWS A COUNTER TO BE TILED.
 REVISE PLAN TO CLARIFY USE OF COUNTER, FBC A 904.
 GENERAL NOTE 1 REGARDING ACCESSIBLE ENTRANCES IS NOT
 CORRECT (60% REQUIRED)
 FLOOR DESIGN LOAD NOT CLEAR; IF THIS IS A CLUBHOUSE
 100PSF REQUIRED
 VARIOUS NOTES REFER TO 170MPH HVHZ; THIS SITE IS 170MPH
 NON-HVHZ AND MUST COMPLY WITH NON-HVHZ REQUIREMENTS
 (HVHZ IS SOMETIMES MORE STRINGENT AND SOMETIMES LESS
 STRINGENT)
 OCCUPANT LOAD OF 100SF PER PERSON MAY NEED TO BE
 REVISED
 IMPACT PROTECTION REQUIRED; PROVIDE INFORMATION
 A NOTE STATES THAT THE ORIGINAL APPROVED PLANS ARE NOT
 AVAILABLE; THEY SHOULD BE ON THE INTERNET
 WWW.FLORIDABUILDING.ORG; CLARIFY
 CHECK ALL NOTES TO CLARIFY SCOPE AND CODE COMPLIANCE
  
 8. THE SITE PLAN SHOWS A ONE STORY CLUBHOUSE,
 HIGHLIGHTED, WHICH IS NOT CONSISTENT WITH THE PLAN
 PROVIDED, CLARIFY, FBC 107.
  
 9. REVISE SITE PLAN TO CLEARLY SHOW ALL PROPERTY LINES,
 DISTANCE OF PROPOSED STRUCTURE TO PROPERTY LINES AND
 ASSUMED PROPERTY LINES (LINES BETWEEN STRUCTURES) FBC
 705. IF THE DARK DASHED LINE IS THE PROPERTY LINE,
 PROVIDE A LEGEND TO DESIGNATE IT AS SUCH.
  
 10. IF THIS STRUCTURE IS TEMPORARY, ADVISE AS TO HOW
 LONG THIS WILL BE IN PLACE OR WHEN THIS WILL BE
 REMOVED, FBC 107 (IMPACT FEES).
  
  