| 2017-06-02 13:49:11 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW COMMENTS: |
| | |
| | 1. PROVIDE OUTLETS PER THE SPACING REQUIREMENTS OF NEC |
| | AND FBC. NEC 210.52(A), FBC RE3901.2 |
| | 2. PROVIDE AFCI PROTECTION FOR LIGHTING AND POWER |
| | OUTLETS INSTALLED. ALL 120-VOLT, SINGLE PHASE, 15 AND |
| | 20 AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS IN DWELLING |
| | UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, |
| | LIBRARIES, DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS, |
| | CLOSETS, HALLWAYS, OR SIMILAR AREAS OR ROOMS, SHALL |
| | HAVE AFCI PROTECTION. NEC 210.12, FBC RE3902.12 |
| | 3. PROVIDE PANEL SCHEDULE, INDICATE ANY NEW OR ALTERED |
| | CIRCUITS, INDICATE WIRE AND BREAKER SIZE. NEC 215.5, |
| | 408.4, FBC 107.2.1 |
| | 4. PROVIDE ELECTRICAL PERMIT APPLICATION WITH SCOPE AND |
| | VALUE OF WORK. FBC 105.1, 109.3 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |