| Plan Review Notes For Permit 17050626 |
| Permit Number |
17050626 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-06-08 10:42:11 | 1 PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | FAC 61G20-3.001 FOR: | | | FLAT ROOF ASSEMBLY. NOTE: MIAMI-DADE NOA 14-1028.02 | | | SUBMITTED IS NOT FOR A FLAT ROOF ASSEMBLY. NOA | | | SUBMITTED IS AN UNDERLAYMENT FOR SHINGLES OR ROOF TILE. | | | NEED TO PROVIDE PRODUCT APPROVAL FOR FLAT ROOF | | | ASSEMBLIES. IN ADDITION, NEED TO CLEARLY SPECIFY WHICH | | | APPROVED ASSEMBLY IS GOING TO BE INSTALLED. AND, NEED | | | TO PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS IF | | | THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES | | | FOR ALL ROOF ZONES. NEED RAS 117 CALCULATIONS TO MEET | | | THE DESIGN PRESSURES REQUIRED BY SEC. R301.1 | | | FBC-RESIDENTIAL. | | | | | | 2- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVAL AS | | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | |
|