| 2017-06-08 11:21:31 | RESIDENTIAL (R3) ADDITION, MECHANICAL REVIEW COMMENTS. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | 1- REVISE EQUIPMENT SIZING CALCULATIONS SUBMITTED. IT |
| | LOOKS LIKE THE CALCULATIONS MAY HAVE BEEN DONE FOR THE |
| | WRONG ADDRESS. THE COVER PAGE SAYS THAT THE HVAC LOAD |
| | CALCULATIONS ARE FOR CHARLES LAWSON AT 807 7TH STREET. |
| | WPB. REVISE CALCULATIONS. PROVIDE THE CORRECT OWNER AND |
| | ADDRESS. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 2- CALCULATIONS SUBMITTED STATE THAT THE HOUSE FACES |
| | SOUTH. THIS BUILDING ORIENTATION LOOKS LIKE IT'S FOR |
| | THE ADDRESS MENTIONED ON ITEM #1 ABOVE NOT FOR THE |
| | HOUSE IN THIS PERMIT APPLICATION. SEE SURVEY OR PBC |
| | PROPERTY APPRAISER WEBSITE FOR THE CORRECT BUILDING |
| | ORIENTATION AND REVISE AS REQUIRED. PROVIDE THE ACTUAL |
| | ORIENTATION OF THE HOUSE IN THIS PERMIT. SEC. R403.6.1 |
| | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | |
| | 3- THE SQUARE FOOTAGE IS INCORRECT. COORDINATE WITH |
| | ITEM #1 ABOVE. NOTE: ACCORDING TO ARCHITECT PLANS |
| | SUBMITTED, THE ADDITION IS GOING TO BE AIR CONDITIONED |
| | WITH AN EXISTING A/C SYSTEM. NEED TO PROVIDE COMPLETE |
| | AND CORRECT EQUIPMENT LOAD CALCULATIONS TO SHOW THAT |
| | THE EXISTING A/C SYSTEM IS ADEQUATE TO SUPPORT THE |
| | ADDITIONAL LOAD. SEC. R403.6.1 FBC-ENERGY CONSERVATION, |
| | 5TH EDITION (2014). NOTE: TO AVOID DELAYS OR CONFLICTS |
| | MAKE SURE LOAD CALCULATIONS TAKE INTO CONSIDERATION THE |
| | CONSTRUCTION TYPE OF THE EXISTING BUILDING AND THE |
| | PROPOSED ADDITION. ONE IS CONCRETE BLOCK AND THE OTHER |
| | ONE IS WOOD FRAME. |
| | |
| | 4- PROVIDE A/C PLAN SHOWING THE DUCTWORK SIZE AND CFMS |
| | FOR THE NEW ADDITION. CLEARLY SPECIFY IF THE EXISTING |
| | UNIT IS ADEQUATE FOR THE ADDITIONAL LOAD OR IF NEW |
| | EQUIPMENT IS INSTALLED. ALSO, LIST THE EQUIPMENT |
| | MANUFACTURER AND MODEL NUMBER SPECIFIED ON THE |
| | EQUIPMENT SIZING CALCULATIONS. NOTE: COORDINATE WITH |
| | ITEM #3 ABOVE. SEC. 107.3.5.3(10) CITY AMENDMENTS. |
| | |
| | 5- PROVIDE 2 COPIES OF EQUIPMENT SIZING CALCULATIONS. |
| | ONLY ONE WAS SUBMITTED AT THIS TIME. SEC. 107.1 CITY |
| | AMENDMENTS. |
| | |
| | 6- MECHANICAL PERMIT IS REQUIRED. SEC. 105.1 CITY |
| | AMENDMENTS. |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ***PLEASE SUBMIT OLD DRAWINGS FOR REFERENCE WHEN NEW |
| | REVISED DRAWINGS ADDRESSING THE COMMENTS ARE SUBMITTED. |
| | |