| Plan Review Notes For Permit 17050594 |
| Permit Number |
17050594 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2017-07-25 12:30:04 | 3RD REVIEW FBC-2014 MECHANICAL | | | PERMIT #17050594 | | | 7/25/17 | | | | | | 1) SHOW BEDROOM RETURNS, AND HOW THE AIR IS BEING | | | RETURNED FROM THE MAIN 16X16 GRILL TO THE AIR HANDLER- | | | SECTION 601.5. | | | | | | 2) SHOW THE BRANCH DUCT SUPPLYING THE KITCHEN AND | | | PROVIDE ALL BRANCH DUCT SIZES. | | | | | | 3) THE DUCT BOARD SHALL BE MINIMUM R-4.2 PER TABLE | | | C403.2.7.1 FBC-14 EBNERGY CONSERVATION. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|