2017-07-25 12:30:043RD REVIEW FBC-2014 MECHANICAL
 PERMIT #17050594
 7/25/17
  
 1) SHOW BEDROOM RETURNS, AND HOW THE AIR IS BEING
 RETURNED FROM THE MAIN 16X16 GRILL TO THE AIR HANDLER-
 SECTION 601.5.
  
 2) SHOW THE BRANCH DUCT SUPPLYING THE KITCHEN AND
 PROVIDE ALL BRANCH DUCT SIZES.
  
 3) THE DUCT BOARD SHALL BE MINIMUM R-4.2 PER TABLE
 C403.2.7.1 FBC-14 EBNERGY CONSERVATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER