Plan Review Notes
Plan Review Notes For Permit 17050594
Permit Number 17050594
Review Stop E
Sequence Number 3
Notes
Date Text
2017-07-27 07:53:55CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS (3RD REVIEW):
  
 1. THIS PREVIOUS COMMENT NOT ADDRESSED: ELECTRICAL PLAN
 IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. FS
 471.003(2)(H); 471.025; FBC 107.2.1
 2. THIS PREVIOUS COMMENT NOT ADDRESSED: PROVIDE PANEL
 SCHEDULE AS PREVIOUSLY REQUESTED, INDICATING NEW OR
 ALTERED CIRCUITS. ANY ALTERED CIRCUITS ARE REQUIRED TO
 HAVE AFCI PROTECTION WHERE NORMALLY REQUIRED PER CODE.
 NEC 210.12, 215.5
 3. THIS PREVIOUS COMMENT NOT ADDRESSED COMPLETELY,
 EXISTING OUTLETS IN DEN-BED ROOM NOT SHOWN, OUTLETS
 NEED TO BE SPACED PER CODE: SHOW REQUIRED OUTLETS WHERE
 POCKET DOOR IS REMOVED AND NEW WALL INSTALLED. NEC
 210.52
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  