Plan Review Notes
Plan Review Notes For Permit 17050594
Permit Number 17050594
Review Stop M
Sequence Number 2
Notes
Date Text
2017-07-03 14:08:342ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17050594
 7/3/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A SCOPE OF WORK OUTLINE ON THE PLAN. CLARIFY
 IF A NEW AC SYSTEM AND DUCTWORK ARE BEING INSTALLED, OR
 WHAT ALTERATIONS TO THE EXISTING SYSTEM ARE PROPOSED.
 SHOW POINTS OF CONNECTION FOR NEW AND EXISTING DUCTWORK
 IF APPLICABLE, AND PROVIDE AN AC EQUIPMENT SCHEDULE.
  
 2) THE PLANS SHALL BEAR THE SIGNATURE OF THE PERSON WHO
 PREPARED THE DESIGN- SECTION 107.2.1 WPB AMENDMENTS TO
 THE FBC.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER