| Date |
Text |
| 2017-07-05 09:24:27 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW COMMENTS: |
| | |
| | 1. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED AND SEALED |
| | BY A DESIGN PROFESSIONAL OR THE ELECTRICAL CONTRACTOR |
| | QUALIFIER. FS 471.003(2)(H); 471.025; FBC 107.2.1 |
| | 2. ELECTRICAL PLAN PROVIDED SHALL BE A MINIMUM 1/8" |
| | SCALE AS PREVIOUSLY REQUESTED. "BUILDING PLANS SHALL BE |
| | DRAWN TO A MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL |
| | PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. THIS POLICY |
| | MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE, |
| | CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORDS |
| | MANAGEMENT." WPB AMENDMENTS TO FBC 107.2.1.4 |
| | 3. PROVIDE PANEL SCHEDULE AS PREVIOUSLY REQUESTED, |
| | INDICATING NEW OR ALTERED CIRCUITS. ANY ALTERED |
| | CIRCUITS ARE REQUIRED TO HAVE AFCI PROTECTION WHERE |
| | NORMALLY REQUIRED PER CODE. NEC 210.12, 215.5 |
| | 4. SHOW REQUIRED OUTLETS WHERE POCKET DOOR IS REMOVED |
| | AND NEW WALL INSTALLED. NEC 210.52 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |