Plan Review Notes
Plan Review Notes For Permit 17050594
Permit Number 17050594
Review Stop E
Sequence Number 2
Notes
Date Text
2017-07-05 09:24:27CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED AND SEALED
 BY A DESIGN PROFESSIONAL OR THE ELECTRICAL CONTRACTOR
 QUALIFIER. FS 471.003(2)(H); 471.025; FBC 107.2.1
 2. ELECTRICAL PLAN PROVIDED SHALL BE A MINIMUM 1/8"
 SCALE AS PREVIOUSLY REQUESTED. "BUILDING PLANS SHALL BE
 DRAWN TO A MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL
 PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. THIS POLICY
 MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE,
 CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORDS
 MANAGEMENT." WPB AMENDMENTS TO FBC 107.2.1.4
 3. PROVIDE PANEL SCHEDULE AS PREVIOUSLY REQUESTED,
 INDICATING NEW OR ALTERED CIRCUITS. ANY ALTERED
 CIRCUITS ARE REQUIRED TO HAVE AFCI PROTECTION WHERE
 NORMALLY REQUIRED PER CODE. NEC 210.12, 215.5
 4. SHOW REQUIRED OUTLETS WHERE POCKET DOOR IS REMOVED
 AND NEW WALL INSTALLED. NEC 210.52
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  