Plan Review Notes
Plan Review Notes For Permit 17050566
Permit Number 17050566
Review Stop M
Sequence Number 2
Notes
Date Text
2017-06-05 09:52:041ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17050566
 6/9/17
  
 RESULTS: DENIED.
  
 1) SHEET M2.01: REVISION #3 DESIGNATED BY LETTER C
 (1.17.2017) WAS NOT INCLUDED IN THE UPDATED PLANS
 SHEET. REVISON #3, AMONG OTHER THINGS, SHOWED THE
 GENERATOR INTAKE AND EXHAUST CLEARANCE DIMENSIONS, AND
 THE LAUNDRY AND NAIL SALON AIR BALANCE CALCULATIONS.
  
 2) M2.02: REVISION #3 DESIGNATED BY LETTER C
 (1.17.2017) WAS NOT INCLUDED IN THE UPDATED PLANS
 SHEET. REVISION #3, AMONG OTHER THINGS, SHOWED
 LOCATIONS OF ABOVE CEILING PLENUM SPACES, AND HAD A
 NOTE PROHIBITING COMBUSTIBLES TO BE INSTALLED IN THE
 MECHANICAL CLOSETS.
  