| Plan Review Notes For Permit 17050566 |
| Permit Number |
17050566 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-06-05 09:52:04 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17050566 | | | 6/9/17 | | | | | | RESULTS: DENIED. | | | | | | 1) SHEET M2.01: REVISION #3 DESIGNATED BY LETTER C | | | (1.17.2017) WAS NOT INCLUDED IN THE UPDATED PLANS | | | SHEET. REVISON #3, AMONG OTHER THINGS, SHOWED THE | | | GENERATOR INTAKE AND EXHAUST CLEARANCE DIMENSIONS, AND | | | THE LAUNDRY AND NAIL SALON AIR BALANCE CALCULATIONS. | | | | | | 2) M2.02: REVISION #3 DESIGNATED BY LETTER C | | | (1.17.2017) WAS NOT INCLUDED IN THE UPDATED PLANS | | | SHEET. REVISION #3, AMONG OTHER THINGS, SHOWED | | | LOCATIONS OF ABOVE CEILING PLENUM SPACES, AND HAD A | | | NOTE PROHIBITING COMBUSTIBLES TO BE INSTALLED IN THE | | | MECHANICAL CLOSETS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|