2017-05-17 07:45:541ST REVIEW FBC-2014 MECHANICAL
 REVISION PERMIT #17050566
 MASTER #15111020
 5/17/17
  
 RESULTS: DENIED.
  
 1) PLAN SHEETS M2.01 & A0.32: A FIRE DAMPER IS REQUIRED
 WHERE THE 12X6 SUPPLY DUCT IS SHOWN PENETRATING A 2HR.
 FIRE RATED WALL IN THE CORRIDOR BY THE LAUNDRY ROOM-
 PLEASE NOTE EXCEPTION #3 UNDER SECTION 716.5.2 FBC-10
 BUILDING APPLIES ONLY TO 1HR RATED WALLS- PROVIDE THE
 REQUIRED FIRE DAMPER.
  
 2) SHEETS M2.02 & A0.33: FIRE DAMPERS ARE REQUIRED
 WHERE THE 26X12 SUPPLY DUCT IS SHOWN PENETRATING THE
 1HR FIRE RATED WALLS AT THE MEP CLOSET AND WOMEN'S
 RESTROOM- PLEASE NOTE EXCEPTION #3 DOES NOT APPLY
 BECAUSE THE DUCT SYSTEM CONTAINS FLEX DUCT BRANCHES.
  
 3) SHEETS M2.02 & A0.33: A FIRE DAMPER IS REQUIRED FOR
 THE 18X10 SUPPLY DUCT PENETRATING THE 1HR FIRE RATED
 YOGA/WOMEN'S RESTROOM WALL BECAUSE THE DUCT SYSTEM
 CONTAINS FLEX BRANCHES.
  
 4) SHEETS M2.22, M2.23, M2.24, M2.25, & M2.26: MANY OF
 THE DUCTS THAT ARE DESIGNATED AS FLAMEBAR PER THE
 ENGINEER'S NARRATIVE ARE NOT IDENTIFIED ON THE PLANS.
 PLEASE LABEL ALL FLAMEBAR DUCTS ON THESE PLAN SHEETS
  
 PLEASE SUBMIT CORRECTED PLANS ALONG WITH THE REQUESTED
 DETAILS AND SUBMITTALS LISTED UNDER PROVISOS #2 & #3.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  