| 2017-05-17 07:45:54 | 1ST REVIEW FBC-2014 MECHANICAL | | | REVISION PERMIT #17050566 | | | MASTER #15111020 | | | 5/17/17 | | | | | | RESULTS: DENIED. | | | | | | 1) PLAN SHEETS M2.01 & A0.32: A FIRE DAMPER IS REQUIRED | | | WHERE THE 12X6 SUPPLY DUCT IS SHOWN PENETRATING A 2HR. | | | FIRE RATED WALL IN THE CORRIDOR BY THE LAUNDRY ROOM- | | | PLEASE NOTE EXCEPTION #3 UNDER SECTION 716.5.2 FBC-10 | | | BUILDING APPLIES ONLY TO 1HR RATED WALLS- PROVIDE THE | | | REQUIRED FIRE DAMPER. | | | | | | 2) SHEETS M2.02 & A0.33: FIRE DAMPERS ARE REQUIRED | | | WHERE THE 26X12 SUPPLY DUCT IS SHOWN PENETRATING THE | | | 1HR FIRE RATED WALLS AT THE MEP CLOSET AND WOMEN'S | | | RESTROOM- PLEASE NOTE EXCEPTION #3 DOES NOT APPLY | | | BECAUSE THE DUCT SYSTEM CONTAINS FLEX DUCT BRANCHES. | | | | | | 3) SHEETS M2.02 & A0.33: A FIRE DAMPER IS REQUIRED FOR | | | THE 18X10 SUPPLY DUCT PENETRATING THE 1HR FIRE RATED | | | YOGA/WOMEN'S RESTROOM WALL BECAUSE THE DUCT SYSTEM | | | CONTAINS FLEX BRANCHES. | | | | | | 4) SHEETS M2.22, M2.23, M2.24, M2.25, & M2.26: MANY OF | | | THE DUCTS THAT ARE DESIGNATED AS FLAMEBAR PER THE | | | ENGINEER'S NARRATIVE ARE NOT IDENTIFIED ON THE PLANS. | | | PLEASE LABEL ALL FLAMEBAR DUCTS ON THESE PLAN SHEETS | | | | | | PLEASE SUBMIT CORRECTED PLANS ALONG WITH THE REQUESTED | | | DETAILS AND SUBMITTALS LISTED UNDER PROVISOS #2 & #3. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|