| 2017-05-24 10:39:37 | 1ST REVIEW FBC-2014 MECHANICAL |
| | SUBMITTAL #17050546 |
| | BRIGHTLINE MASTER #16070715 |
| | 5/24/17 |
| | |
| | 1) EF-25-1: THE SUBMITTAL FOR THE PENNBARRY D10 SMOKE |
| | EXHAUST FAN DOES NOT PROVIDE EVIDENCE THAT THE FAN IS |
| | RATED AND CERTIFIED BY THE MANUFACTURER FOR THE |
| | PROBABLE TEMPERATURE RISE AS REQUIRED BY SECTION |
| | 513.10.1 FBC-14 MECHANICAL. THE SUBMITTAL DOES NOT |
| | INDICATE THE FAN IS UL 705 LISTED AND LABELED PER THE |
| | ENGINEER'S NOTES IN THE FAN SCHEDULE (SHEET M1301), AND |
| | DOES NOT INDICATE THE FAN WILL BE EQUIPPED WITH TWO |
| | BELTS. PLEASE REVIEW THE SUBMITTAL FOR COMPLIANCE. |
| | |
| | 2) DUCTS: REFER TO SECTION 513.10.2 FBC-14 MECHANICAL |
| | AND INDICATE WHICH DUCTS IN THE SUBMITTAL PACKAGE ARE |
| | DESIGNATED FOR SMOKE CONTROL AND EXHAUST, AND PROVIDE |
| | EVIDENCE THAT THE DESIGNATED DUCTS HAVE BEEN TESTED FOR |
| | RESISTANCE TO TEMPERATURE RISE AND PRESSURE, AND LEAK |
| | TESTED TO 1.5 TIMES THE MAXIMUM DESIGN PRESSURE. |
| | |
| | 3) IT DOES NOT APPEAR THAT THE PENNBARRY SMOKE CONTROL |
| | FAN SUBMITTALS INDICATE THAT THE SELECTED SMOKE CONTROL |
| | FANS ARE EQUIPPED WITH TWO BELTS AS REQUIRED BY SECTION |
| | 513.10.5 FBC-14 MECHANICAL, AND ALSO BY THE ENGINEER OF |
| | RECORD'S DESIGN- SEE SUBMITTAL REVIEW COMMENTS BY C. |
| | BUI. |
| | |
| | 4) PLEASE REVISE THE FAN SCHEDULE ON THE PLAN TO MATCH |
| | THE SUBMITTALS. |
| | |
| | 5) MOTORIZED DAMPERS: THE SUBMITTAL FOR THE DUROZONE |
| | MOTORIZED DAMPER DOES NOT INDICATE THE UNIT IS CLASS 1A |
| | RATED AND, DOES NOT EXCEED THE MAXIMUM LEAKAGE RATE |
| | WHEN TESTED IN ACCORDANCE WITH AMCA 500D- SEE SECTION |
| | C402.4.5.2 FBC-14 ENERGY CONSERVATION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |