| Plan Review Notes For Permit 17050545 |
| Permit Number |
17050545 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-06-06 12:36:09 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #17050545 | | | 6/6/17 | | | | | | RESULTS: DENIED. | | | | | | 1) HVAC NOTE #11 INDICATES THE PLAN IS INTENDED TO BE | | | AN "AS-BUILT OF CONTRACTOR DESIGN", HOWEVER NO DUCTWORK | | | LATYOUT AND DETAILS HAVE BEEN PROVIDED. | | | | | | 2) PROVIDE BATH EXHAUST DUCT DETAILS- TYPE AND SIZE OF | | | DUCTS AND SUBDUCT CONNECTIONS TO EXISTING CHASES. | | | | | | 3) THE ARCHITECT OF RECORD SHALL PROVIDE HIS SIGNATURE | | | AND SEAL ON BOTH SETS OF PLANS SUBMITTED IN ACCORDANCE | | | WITH SECTION 61G1-16.003 FLORIDA ADMINISTRATIVE CODE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|