| Plan Review Notes For Permit 17050545 |
| Permit Number |
17050545 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-05-18 14:49:08 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17050545 | | | 5/18/17 | | | | | | RESULTS: DENIED. | | | | | | 1) EXHAUST VENTILATION FOR THE KITCHEN IS REQUIRED PER | | | TABLE 403.3. PROVIDE A SYSTEM THAT PROVIDES EITHER 25 | | | CFMS CONTINUOUSLY, OR 100 CFMS INTERMITTENTLY. | | | | | | 2) PROVIDE PRODUCT SPEC SHEETS FOR THE NEW RANGE AND | | | RANGE HOOD AND INCLUDE EQUIPMENT SCHEDULES ON THE PLAN- | | | SECTION 505. | | | | | | 3) SHOW THE EXHAUST DUCT RUN AND TERMINATION LOCATION. | | | PLEASE INCLUDE THE TYPE AND SIZE OF DUCT. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|