| 2017-05-16 06:34:48 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | 1. FBC B 603, DETAIL A-A1.0 SPECS WOOD AS ALTERNATE, |
| | ISN'T THIS A HIGH RISE? REVISE DETAIL OR CLARIFY. |
| | |
| | 2. DEMOLITION NOTES, REMOVE NOTES NOT APPLICABLE TO |
| | THIS PROJECT (BURIED TANKS, SOIL TESTING, ETC.). |
| | |
| | 3. PROVIDE TEST REPORTS FOR UNDERLAYMENT; THREE |
| | REQUIRED SHOWING COMPLIANCE WITH: |
| | |
| | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| | THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM |
| | CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED |
| | GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723. |
| | |
| | 4. FLOOR PLANS 1 AND 2, PAGE A1.0 APPEAR TO PROPOSE A 4 |
| | INCH CHANGE IN ELEVATION TO THE AREA SOUTH OF THE |
| | KITCHEN. IF THIS IS INTENDED FOR THE COUNTERTOP, |
| | RE-LOCATE THE DIMENSION AND REVISE ELEVATIONS C AND E. |
| | |
| | IF THIS IS FOR THE FLOOR - THE PURPOSE OF THIS IS NOT |
| | CLEAR, NO CORRESPONDING DETAIL PROVIDED, ROOM |
| | DESIGNATION FOR THE AREA NOT PROVIDED. FBC B CHAPTER |
| | 10, FBC 107, REVISE TO CLARIFY. |
| | |
| | |