| Plan Review Notes For Permit 17050544 |
| Permit Number |
17050544 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-05-12 16:39:46 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17050544 | | | 5/12/17 | | | | | | RESULTS: DENIED. | | | | | | 1) SHEET M400: PLEASE TAG THE SUPPLY DIFFUSERS AND | | | RETURN GRILLS IN ACCORDANCE WITH THE AIR DISTRIBUTION | | | SCHEDULE ON THE APPROVED SHEET 200. PLEASE NOTE THE | | | APPROVED HVAC FLOOR PLAN WAS LABELED M100. | | | | | | 2) M200: REVISE THE HEAT PUMP SCHEDULE N THE APPROVED | | | M200 PLAN SHEET TO SHOW THE NEW HEAT PUMPS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|