| Notes |
| Date |
Text |
| 2017-05-17 09:39:38 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17050529 | | | 5/17/17 | | | | | | 1) THE CITY OF WEST PALM BEACH BUILDING DEPARTMENT | | | REQUIRES SMOKE DETECTORS IN THE RETURN AIR SYSTEMS OF | | | ANY 5-TON AC SYSTEM UNLESS PRODUCT SPECIFICATIONS FROM | | | THE MANUFACTURER INDICATE THE SYSTEM CANNOT PRODUCE | | | OVER 2000 CFMS OF SUPPLY AIR.- SEE SECTION 606.2.1. | | | | | | 2) THE ENERGYGAUGE MANDATORY REQUIREMENTS CHECKLIST | | | INDICATES COMPLIANCES FOR AN ERV, AIR AND WATER | | | ECONOMIZERS, AND A COOLING TOWER, NONE OF WHICH APPEAR | | | TO BE APPLICABLE TO THE PROPOSED PROJECT WITH THE | | | EXCEPTION OF THE AIR ECONOMIZER- PLEASE CORRECT. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|