Plan Review Notes
Plan Review Notes For Permit 17050529
Permit Number 17050529
Review Stop M
Sequence Number 1
Notes
Date Text
2017-05-17 09:39:381ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17050529
 5/17/17
  
 1) THE CITY OF WEST PALM BEACH BUILDING DEPARTMENT
 REQUIRES SMOKE DETECTORS IN THE RETURN AIR SYSTEMS OF
 ANY 5-TON AC SYSTEM UNLESS PRODUCT SPECIFICATIONS FROM
 THE MANUFACTURER INDICATE THE SYSTEM CANNOT PRODUCE
 OVER 2000 CFMS OF SUPPLY AIR.- SEE SECTION 606.2.1.
  
 2) THE ENERGYGAUGE MANDATORY REQUIREMENTS CHECKLIST
 INDICATES COMPLIANCES FOR AN ERV, AIR AND WATER
 ECONOMIZERS, AND A COOLING TOWER, NONE OF WHICH APPEAR
 TO BE APPLICABLE TO THE PROPOSED PROJECT WITH THE
 EXCEPTION OF THE AIR ECONOMIZER- PLEASE CORRECT.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  