Plan Review Notes
Plan Review Notes For Permit 17050529
Permit Number 17050529
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-05-22 15:08:43PERMIT #17050529
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) FOR ASSEMBLY AND EDUCATIONAL OCCUPANCIES WITH AN
 OCCUPANT LOAD OF 100 OR MORE PERSONS (50 PERSONS PER
 THE FLORIDA BUILDING CODE), PANIC HARDWARE SHALL BE
 PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH. NO OTHER
 LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT BE
 RELEASED BY THE PANIC HARDWARE. AS A SUBSTITUTE FOR
 PANIC HARDWARE, THE MAIN ENTRANCE IS PERMITTED TO HAVE
 AN INTERIOR KEYED DOOR LOCK (AND NO LATCH) WITH A
 READILY VISIBLE SIGN STATING THIS DOOR TO REMAIN
 UNLOCKED WHEN THE BUILDING IS OCCUPIED. SIGN LETTERS
 SHALL BE AT LEAST 1 INCH IN HEIGHT. A THUMB TURN STYLE
 LOCK IS NOT PERMITTED TO BE SUBSTITUTED FOR A KEYED
 LOCK.
  
 2) DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY
 THE FIRE DEPARTMENT AFTER ALL OTHER PLAN REVIEWER
 COMMENTS HAVE BEEN SATISFIED.
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE