| 2017-05-25 07:55:43 | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION |
| | |
| | 110.24 AVAILABLE FAULT CURRENT. |
| | (A) FIELD MARKING. SERVICE EQUIPMENT IN OTHER THAN |
| | DWELLING UNITS SHALL BE LEGIBLY MARKED IN THE FIELD |
| | WITH THE |
| | MAXIMUM AVAILABLE FAULT CURRENT. THE FIELD MARKLNG(S) |
| | SHALL |
| | INCLUDE THE DATE THE FAULT-CURRENT CALCULATION WAS |
| | PERFORMED |
| | AND BE OF SUFFICIENT DURABILITY TO WITHSTAND THE |
| | ENVIRONMENT |
| | INVOLVED. |
| | |
| | (B) MODIFICATIONS. WHEN MODIFICATIONS TO THE ELECTRICAL |
| | INSTALLATION OCCUR THAT AFFECT THE MAXIMUM AVAILABLE |
| | FAULT |
| | CURRENT AT THE SERVICE, THE MAXIMUM AVAILABLE FAULT |
| | CURRENT |
| | SHALL BE VERIFIED OR RECALCULATED AS NECESSARY TO |
| | ENSURE THE |
| | SERVICE EQUIPMENT RATINGS ARE SUFTICIENT FOR THE |
| | MAXIMUM |
| | AVAILABLE FAULT CULTENT AT THE LINE TERMINALS OF THE |
| | EQUIPMENT. |
| | THE REQUIRED FIELD MARKING(S) IN LLO.24(A) SHALL BE |
| | ADJUSTED TO |
| | REFLECT THE NEW LEVEL OF MAXIMUM AVAILABLE FAULT |
| | CURRENT |
| | |
| | 408.4 FIELD IDENTIFICATION REQUIRED. |
| | (B) SOURCE OF SUPPLY. ALL SWITCHBOARDS,SWITEHGEAR, AND |
| | PANELBOARDS SUPPLIED BY A FEEDER(S) IN OTHER THAN ONE- |
| | OR |
| | TWO-FAMILY DWELLINGS SHALL BE MARKED TO INDICATE EACH |
| | DEVICE |
| | OR EQUIPMENT WHERE THE POWER ORIGINATES |
| | |
| | C405.2 LIGHTING CONTROLS (MANDATORY). |
| | LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS |
| | SPECIFIED |
| | IN SECTIONS C405.2.1, C405.2.2, C405.2.3 AND C405.2.4. |
| | |
| | C405.2.1 MANUAL LIGHTING CONTROLS. |
| | ALL BUILDINGS SHALL INCLUDE MANUAL LIGHTING CONTROLS |
| | THAT MEE |
| | THE REQUIREMENTS OF SECTIONS C405.2.1.1 AND C405.2.1.2. |
| | |
| | C405.2.1.1 INTERIOR LIGHTING CONTROLS. |
| | EACH AREA ENCLOSED BY WALLS OR FLOOR-TO-CEILING |
| | PARTITIONS SHAL |
| | HAVE AT LEAST ONE MANUAL CONTROL FOR THE LIGHTING |
| | SERVING THAT AREA. |
| | THE REQUIRED CONTROLS SHALL BE LOCATED WITHIN THE AREA |
| | SERVED BY |
| | THE CONTROLS OR BE A REMOTE SWITCH THAT IDENTIFIES THE |
| | LIGHTS SERVED |
| | AND INDICATES THEIR STATUS |
| | |