2017-07-20 09:05:391) CITY RECORDS SHOW AN EXISTING GAS SYSTEM WITH AN
 EXISTING BTU LOAD OF 540,000 BTU'S. THE ADDED 281,000
 BTU'S BRINGS THE TOTAL TO 821,000 BTU'S. THE GALVANIZED
 SUPPLY LINE FROM THE METER SHALL BE A MINIMUM OF 2
 INCHES FOR A LESS THAN 2 PSI SYSTEM PER TABLE 402.4 (2)
 . THE PLANS ON RECORD SHOWS THIS SUPPLY AS 1 1/2
 INCHES.
 2) ONE OF THE PE TABLES REFERENCED ON THE DRAWING
 (TABLE 402.4 (24) IS FOR PE TUBING WITH A MAX SIZE OF
 3/4 INCH. THIS TABLE IS NOT APPLICABLE.
 3) THE PLANS INDICATE AN EXISTING GAS METER. THE BTU
 LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE
 TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
  
 NOTE; I HAVE INCLUDED A COPY OF THE PLAN ON CITY FILE
 FOR YOUR INFORMATION.
  
  