| Plan Review Notes For Permit 17050508 |
| Permit Number |
17050508 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-06-05 07:47:28 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING - COMMENTS FROM THE FIRST REVIEW | | | WERE NOT ADDRESSED | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE GENERATOR PAD WINDLOAD ANCHORING DETAILS FROM | | | RONALD H. WILSON A FLORIDA LICENSED ENGINEER ARE | | | REQUIRED TO HAVE HIS ORIGINAL HANDWRITTEN SIGNATURE IN | | | ADDITION TO HIS SEAL AND THE DATE. COPIES OR OTHER | | | FACSIMILES ARE NOT ACCEPTABLE. FAC 61G15-23.002 | | | | | | 2) A MINIMUM OF TWO IDENTICAL SETS OF PLAN DOCUMENTS | | | ARE REQUIRED. SEE GAS REVIEW COMMENTS. FBC 107.1 | | | |
|