| 2017-05-25 06:21:15 | 1) THERE ARE 4 SETS OF DOCUMENTS THAT HAVE BEEN | | | SUBMITTED AND ALL THE SETS DO NOT CONTAIN THE SAME | | | SHEETS. ORGANIZE THE SUBMITTAL DOCUMENTS INTO COMPLETE | | | SETS FOR REVIEW. WPB AMEND. TO FBC SEC. 107.2.1. | | | 2) THE SURVEY AND ONE OF THE GAS PLANS SHOWS 1 INCH | | | UNDERGROUND PE AND ANOTHER GAS DRAWING SHOWS 3/4 INCH | | | PE. CLARIFY. | | | 3) ONE OF THE GAS PLANS SHOWS A BTU LOAD OF 330,000 | | | BTU'S BUT THE MANUF. SPEC SHEETS FOR THE GENERATOR | | | SHOWS 281,000 BTU'S AT FULL LOAD. CLARIFY. | | | 4) THE GAS APPLICATION NOTES A NEW GAS METER UNDER THE | | | DESCRIPTION OF WORK BUT THE PLANS SHOW AN EXISTING GAS | | | METER. CLARIFY. | | | 5) THE GAS PLAN SHOWS A LOW PRESSURE SYSTEM BUT YOU | | | HAVE ALSO SUBMITTED A SIZING TABLE FOR A 2 PSI SYSTEM. | | | IF THIS IS NOT APPLICABLE REMOVE COPIES OF THIS | | | DOCUMENT FROM THE PLANS. WPB AMEND. TO FBC SEC.107.2.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|