Plan Review Notes
Plan Review Notes For Permit 17050506
Permit Number 17050506
Review Stop M
Sequence Number 1
Notes
Date Text
2017-05-12 11:38:311ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17050506
 5/12/17
  
 RESULTS: DENIED.
  
 1) PROVIDE EQUIPMENT SCHEDULES FOR THE CHILLER AND THE
 WATER TANK ON THE PLAN. THE CHILLER SCHEDULE MUST
 INCLUDE THE EFFICIENCY RATING OF THE UNIT AS REQUIRED
 BY TABLE C403.2.3(7) FBC-14 ENERGY CONSERVATION.
  
 2) SUBMIT A CUT SHEET FOR THE WATER TANK.
  
 3) THE CHILLER APPEARS TO BE ON THE ROOF: PROVIDE WIND
 LOAD ENGINEERING FOR INSTALLATION- SECTION 301.15.
  
 4) SUBMIT TWO COPIES OF THE CITY OF WEST PALM BEACH AC
 CHANGEOUT FORM,
  
 5) PROVIDE THE TYPE AND THICKNESS OF CHILLED WATER
 PIPING INSULATION- REFER TO TABLE C403.2.8.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER