2017-05-17 15:07:251ST REVIEW FBC-2014 MECHANICAL
 REVISION PERMIT #17050436
 MASTER #15081154
 5/17/17
  
 1) (AC A-01) HAS BEEN CHANGED TO A 2.0 TON UNIT IN THE
 SCHEDULE (SHEET M101) BUT IS LABELED AS A 4.0 TON UNIT
 ON THE LAYOUT PLAN (M301).
  
 2) M301, UNIT A-1ST LEVEL: SHOW THE CFMS AT EACH SUPPLY
 DIFFUSER AND AND RETURN GRILL.
  
 3) REVISE THE ENERGY CALCULATIONS TO SHOW THE CHANGE IN
 SYSTEMS (AC A0-1) & (AC A0-2) PER THE REVISED SCHEDULE
 ON M101.
  