| Plan Review Notes For Permit 17050420 |
| Permit Number |
17050420 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2018-03-27 11:14:17 | 1) THE WATER SUPPLY VALVES FOR THE STACKABLE | | | WASHER/DRYER SHALL BE ACCESSIBLE PER THE 2014 | | | FBC-PLUMBING SEC.606.3. | | | 2) INDICATE ON THE PLANS WHERE THE TRENCH DRAIN FROM | | | THE DUMPSTER DISCHARGES. | | | 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE LINT | | | INTERCEPTOR. WPB AMEND. TO FBC SEC. 107.2.1. | | | 4) THE CLOTHES WASHER SHALL DISCHARGE TO A MINIMUM 3 | | | INCH STACK. 2014 FBC-PLUMBING SEC. 406.2. | | | 5) SHOW THE LINT INTERCEPTOR ON THE SANITARY RISER. WPB | | | AMEND. TO FBC SEC. 107.2.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|