Plan Review Notes
Plan Review Notes For Permit 17050420
Permit Number 17050420
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2018-02-28 10:28:40THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE FIRE SPRINKLER SYSTEM IS REQUIRED TO BE
 MONITORED AND SUPERVISED PER NFPA 101 AND THE BUILDING
 CODE.
  
  
 NFPA 101, CHAPTER 9,
  
 9.6 FIRE DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 9.6.1* GENERAL.
 9.6.1.1 THE PROVISIONS OF SECTION 9.6 SHALL APPLY ONLY
 WHERE SPECIFICALLY REQUIRED BY ANOTHER SECTION OF THIS
 CODE OR WHERE SUPERVISION OF A NEW FIRE SPRINKLER
 SYSTEM OR NEW FIRE ALARM SYSTEM IS REQUIRED BY THE
 FLORIDA BUILDING CODE.
  
  
 9.7.2 SUPERVISION.
 9.7.2.1* SUPERVISORY SIGNALS.
 9.7.2.1.1 WHERE SUPERVISED AUTOMATIC SPRINKLER SYSTEMS
 ARE REQUIRED BY ANOTHER SECTION OF THIS CODE,
 SUPERVISORY ATTACHMENTS SHALL BE INSTALLED AND
 MONITORED FOR INTEGRITY IN ACCORDANCE WITH NFPA 72,
 NATIONAL FIRE ALARM AND SIGNALING CODE, AND A
 DISTINCTIVE SUPERVISORY SIGNAL SHALL BE PROVIDED TO
 INDICATE A CONDITION THAT WOULD IMPAIR THE SATISFACTORY
 OPERATION OF THE SPRINKLER SYSTEM.
  
 FL BUILDING CODE
  
 901.6 SUPERVISORY SERVICE.
  
 WHERE REQUIRED, FIRE PROTECTION SYSTEMS SHALL BE
 MONITORED BY AN APPROVED SUPERVISING STATION IN
 ACCORDANCE WITH NFPA 72.
  
 901.6.1 AUTOMATIC SPRINKLER SYSTEMS.
  
 AUTOMATIC SPRINKLER SYSTEMS SHALL BE MONITORED BY AN
 APPROVED SUPERVISING STATION.
  
  
  
 PLEASE ENSURE THE REQUIRED COMPLIANCE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  