| 2018-02-28 10:28:40 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| | |
| | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| | INSPECTION. |
| | |
| | |
| | 1) THE FIRE SPRINKLER SYSTEM IS REQUIRED TO BE |
| | MONITORED AND SUPERVISED PER NFPA 101 AND THE BUILDING |
| | CODE. |
| | |
| | |
| | NFPA 101, CHAPTER 9, |
| | |
| | 9.6 FIRE DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. |
| | 9.6.1* GENERAL. |
| | 9.6.1.1 THE PROVISIONS OF SECTION 9.6 SHALL APPLY ONLY |
| | WHERE SPECIFICALLY REQUIRED BY ANOTHER SECTION OF THIS |
| | CODE OR WHERE SUPERVISION OF A NEW FIRE SPRINKLER |
| | SYSTEM OR NEW FIRE ALARM SYSTEM IS REQUIRED BY THE |
| | FLORIDA BUILDING CODE. |
| | |
| | |
| | 9.7.2 SUPERVISION. |
| | 9.7.2.1* SUPERVISORY SIGNALS. |
| | 9.7.2.1.1 WHERE SUPERVISED AUTOMATIC SPRINKLER SYSTEMS |
| | ARE REQUIRED BY ANOTHER SECTION OF THIS CODE, |
| | SUPERVISORY ATTACHMENTS SHALL BE INSTALLED AND |
| | MONITORED FOR INTEGRITY IN ACCORDANCE WITH NFPA 72, |
| | NATIONAL FIRE ALARM AND SIGNALING CODE, AND A |
| | DISTINCTIVE SUPERVISORY SIGNAL SHALL BE PROVIDED TO |
| | INDICATE A CONDITION THAT WOULD IMPAIR THE SATISFACTORY |
| | OPERATION OF THE SPRINKLER SYSTEM. |
| | |
| | FL BUILDING CODE |
| | |
| | 901.6 SUPERVISORY SERVICE. |
| | |
| | WHERE REQUIRED, FIRE PROTECTION SYSTEMS SHALL BE |
| | MONITORED BY AN APPROVED SUPERVISING STATION IN |
| | ACCORDANCE WITH NFPA 72. |
| | |
| | 901.6.1 AUTOMATIC SPRINKLER SYSTEMS. |
| | |
| | AUTOMATIC SPRINKLER SYSTEMS SHALL BE MONITORED BY AN |
| | APPROVED SUPERVISING STATION. |
| | |
| | |
| | |
| | PLEASE ENSURE THE REQUIRED COMPLIANCE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |