2018-03-06 13:21:422014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17050420
 ADD: 5215 S. DIXIE HWY.
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-523-1815
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 3RD REVIEW
 DATE: TUES. MARCH 06/2018
 ACTION: DENIED
  
 1) COMPLIED. UNITY OF TITLE FOR LOTS 5215, 5207 S.
 DIXIE AND 407 PUTNAM RD.
  
 2) COMPLIED: . 108.3* BUILDING PERMIT VALUATION.
 FEE VALUE LOW. BASED ON THE CURRENT IIC TABLES FEB. 01/
 2017 THE VALUES ARE AS STATED:
 BUILDING IIB/ FIRE SPRINKLERED
 VET OFFICE 1097 SQ. FT. X $161.91= $177,615.00
 MERCANTILE 4083 SQ. FT. X $117.10= $478,119.00
 TOTAL DOLLAR AMOUNT $655,734.00
 ADJUSTED VALUE FOR LISTED PERMITS BELOW $560,110.00.
  
 PLEASE DEDUCT THE FIRE SPRINKLER FOR BUILDING ONLY, AND
 FIRE ALARM FOR BUILDING AND ANY LOW VOLTAGE PERMIT FOR
 THE BUILDING. THE MECHANICAL, ELECTRIC, PLUMBING AND
 ROOFING ARE EACH $80.00 SUB-PERMITS WITH THEIR VALUE
 UNDER THE PRIME PERMIT.
  
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK
 STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE,
 LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE
 BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR
 THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE
 PRIME OR MASTER PERMIT.
  
 3A) PROVISO: ONCE THE NEW ANIMAL HOSPITAL IS COMPLETE,
 THE CONTRACTOR HAS TO REQUEST A TCO, (TEMPORARY
 CERTIFICATE OF OCCUPANCY). A FEE OF $500.00 DOLLARS IS
 INVOLVED AND IS GOOD FOR ONLY 90 DAYS. IF THE REMAINDER
 OF THE BUILDING IS NOT COMPLETE WITHIN 90 DAYS A 2ND
 REQUEST FOR TCO WILL NEED TO CONTINUE TO OCCUPY THE
 ANIMAL HOSPITAL AND AN ADDITIONAL FEE OF $500.00 WOULD
 BE REQUIRED. IF AFTER (2) CERTIFICATES THE BUILDING IS
 NOT COMPLETE, THE CONTRACTOR WILL THEN NEED TO APPLY TO
 THE BOARD OF ADJUSTMENT AND APPEAL FOR THE CONTINUATION
 OF THE TCO, FEES ASSOCIATED WITH THE BOARD OF
 ADJUSTMENT & APPEAL ARE $100.00.
  
 3B)PROVISO: THE DESIGNER OF RECORD HAS SPOKEN WITH MR.
 SWOOPE AND MR. SWOOPE STATED THE IMPACT FEE ASSESSMENTS
 AND CREDITS WOULD FOLLOW THE FOLLOWING PLAN:
 PHASE 1- ASSESSMENT FOR IMPACT FEES FOR PHASE 1
 CONSTRUCTION.
 PHASE 2- CREDITS FOR THE DEMOLITION OF THE EXISTING VET
 OFFICE.
 PHASE 3- ASSESSMENT FOR RETAIL LESS CREDITS FOR THE
 EXISTING VET CLINIC EQUALS NET IMPACT FEES DUE FOR THE
 RETAIL.
  
 3C) 3RD REQUEST. 4X FEE / NOTICE!!!!! FLORIDA STATUTE
 553.80(2)(B) .
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 OF THE 3 SETS OF PLANS, THE ONE SET MARKED FOR
 ENGINEERING SHOWS THE NEW CORRECTED FS-1 PLAN. PLEASE
 NOTE ONLY ONE SET OF PLANS UPDATES WITH NEW FIRE
 SPRINKLER PLANS. THE THIRD ISSUE THAT WILL NEED TO BE
 CORRECTED IS FOUND ON THE FS-1 PLAN. AS DEPICTED THE
 FIRE LINE WILL NOT BE INSTALLED UNTIL THE PHASE III
 SINCE IT IS SHOWN GOING THROUGH THE SOUTH END OF THE
 BUILDING. THE FIRE SPRINKLER WILL NEED TO BE IN THE
 ANIMAL HOSPITAL IN PHASE ONE! THE PLAN NEEDS TO BE
 ROUTED IN A WAY THAT THE FIRE LINE ENTERS THE BUILDING
 AT PHASE ONE AND THEN IS EXTENDED IN PHASE III.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 3D) 2ND REQUEST. THE SET MARKED FOR ENGINEERING IS
 MISSING THE COVERSHEET A0.00.
  
 3E) 2ND REQUEST. THE SET MARKED FOR ENGINEERING IS
 MISSING A7.01 & A8.00
  
 3F) 2ND REQUEST. THE SET MARKED FOR ENGINEERING IS
 MISSING SHEET S3.3 IN ONE SET OF PLANS.
  
 3G) 2ND REQUEST. THE 1 SET OF PLANS MARKED FOR
 ENGINEERING HAS C1-C6 DATED 09/28/17/ (2) SETS OF
 PLANS ARE MISSING THE CIVIL DRAWINGS C1-C6.
  
 4-6) COMPLIED.
  
 7) 2ND REQUEST. SHEET S2.1 UPPER RIGHT CORNER OF THE
 SHEET, NOTES INDICATE THE USE OF 5/8 INCH PERFORMANCE
 RATED PLYWOOD. SHEET S3.3 NOTES 5 & 8 BOTH INDICATE THE
 USE OF 5/8 INCH PLYWOOD. THE DESIGNER OF RECORD HAS
 DESIGNED THIS BUILDING TO BE CONSTRUCTION TYPE II-B. IN
 THE 2014 FBC-B SECTION 603.1.1.1.3 FIRE RETARDANT
 TREATED WOOD SHALL BE PERMITTED IN ROOF CONSTRUCTION
 INCLUDING, GIRDERS, TRUSSES, FRAMING, AND DECKING.
 PLEASE CORRECT THE PLANS, TO FIRE RETARDANT TREATED
 WOOD.
  
 DETAILS STILL SHOWING EITHER 5/8 INCH CDX PLYWOOD OR ?
 INCH PLYWOOD AND WOOD TRUSSES ON THE TOWERS:
  
 7A) A5.01 DETAIL 3 5/8 INCH CDX PLYWOOD , WOOD OR METAL
 TRUSSES.
  
 7B) SHEETS, A4.00 NOTE #9 , A4.01 NOTE # 9 & A5.00 NOTE
 # 9 ALL STATE ? INCH CDX PLYWOOD WITH EITHER WOOD OR
 METAL TRUSSES.
  
 7C) SHEET S1.1 HEADING: PRE-ENGINEERED WOOD TRUSSES
 7D) SHEET 52.1 NOTES ON PLYWOOD AT LIGHT GAUGE NOTES
 5/8 INCH PLYWOOD.
  
 7E) SHEET S2.2 HIGH ROOF FRAMING WOOD TRUSSES AND 5/8
 INCH SHEATHING, NOTE 2 5/8 INCH WOOD SHEATHING
  
 7F) SHEET S3.3 DETAIL 5, 8, & 9 ALL INDICATE THE USE OF
 PLYWOOD SHEATHING. SEE COMMENT (3F).
  
 8) SEMI-COMPLIED. SHEET S2.1 THE BOTTOM TOWER (SOUTH)
 HAS A WALL SECTION DETAIL # 8/ S3.2. THE WALL SECTION
 ON THE OTHER SIDE OF THE TOWER DETAIL # 9/ S3.3,
 MISSING SHEET S3.3. DISCREPANCY IN PLANS.
  
 8A) DETAIL 8/S3.2 IS THE ROOF TOP CURB NOT THE WALL
 SECTION ON THE BAR JOIST, PLEASE CORRECT.
  
 8B) STILL MISSING THE S3.3 IN THE 3RD SET OF PLANS
 INDICATING ENGINEERING. . SEE COMMENT (3F).
  
 9) 2ND REQUEST. SHEET A 5.01 DETAIL # 3 THE UPPER ROOF
 DETAIL INDICATES SHEATHING IS TO BE ATTACHED TO
 PRE-FABRICATED WOOD TRUSSES OR METAL ROOF TRUSSES REFER
 TO STRUCTURAL DRAWINGS. 2014 WEST PALM BEACH AMENDMENTS
 TO THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.2.1.3: W.P.B. ADMINISTRATIVE CODE/2014 DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR
 IN PART, OR, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE
 USED AS A SUBSTITUTE FOR SPECIFIC INFORMATION".
  
 10-11) PROVISO/ DEFERRED SUBMITTAL. 107 .3.4.2. SHEET
 S3.2 SHOWS DETAIL # 8 THE CURB DETAIL FOR RTU SUPPORT.
 THE DETAIL DOES SHOW THE ATTACHMENT OF THE CURB TO THE
 ROOF FRAMING MEMBERS AND A MAXIMUM CURB HEIGHT OF 14
 INCHES FROM THE FINISH ROOF DECK TO THE TOP OF THE
 CURB, THE DETAIL DOES NOT SHOW THE OVERLAP OF THE TOP
 OF THE RTU CURB, AS DETAILED ON M3. THE BOTTOM OF THE
 RTU UNIT (OVERLAP) HAS TO BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES (203 MM) ABOVE THE ROOF SURFACE, OR
 WHERE ROOFING MATERIALS EXTEND BENEATH THE UNIT. FBC-B
 1509.6.5 MECHANICAL UNITS.
  
  
 12) 3RDND REQUEST. 4X FEE / NOTICE!!!!! FLORIDA STATUTE
 553.80(2)(B)
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 RESPONSE INDICATES REFER TO THE ATTACHED DENSEGLASS
 FLORIDA PRODUCT APPROVAL.
 SHEET A 5.00 NOTE 25 INDICATES THE USE OF 5/8 INCH
 DENSGLASS SHEATHING, PROVIDE A PRODUCT APPROVAL SHOWING
 THE TESTING AND TO WHAT DESIGN PRESSURES THE DENSGLASS
 CAN BE INSTALLED. 1609.6.4.4.1 COMPONENTS & CLADDING.
 RESPONSE INDICATES SEE ATTACHED DENSGLASS PRODUCT
 APPROVAL. THERE WERE NO PRODUCT APPROVALS AT ALL IN
 THIS SUBMISSION, THIS CAN BE A DEFERRED SUBMITTAL.
  
 13) PROVISO/ DEFERRED SUBMITTAL. 107 .3.4.2. 2014 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, FLAT AND SLOPED
 ROOFING, CURBS, ROOF TOP VENTILATORS
  
 14) PROVISO/ DEFERRED SUBMITTAL. 107 .3.4.2. IDENTIFY
 GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE PRODUCT
 APPROVAL BEFORE SUBMITTING TO DESIGNER OF RECORD AND
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL
 PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE OPENING
 WIDTH & HEIGHT, TYPE OF GLAZING, MULLION INFORMATION IF
 REQUIRED, ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH
 OPENING SIZE. 2014 FBC-B 1405.13.1 INSTALLATION.
 WINDOWS AND DOORS SHALL BE INSTALLED IN ACCORDANCE WITH
 APPROVED MANUFACTURERS INSTRUCTIONS. FASTENER SIZE AND
 SPACING SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND
 SHALL BE CALCULATED BASED ON MAXIMUM LOADS AND SPACING
 USED IN THE TESTS.
  
 15) PROVISO/ DEFERRED SUBMITTAL. 107 .3.4.2. FBC
 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015
 (2) THE ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND
 REVIEWING ALL PROJECT DATA, REPORTS, SHOP DRAWINGS
 ETC..
  
 16) PROVISO/ DEFERRED SUBMITTAL. 107 .3.4.2. PROVISO/
 DEFERRED SUBMITTAL. 107 .3.4.2.
 EFIS SYSTEMS: PLEASE PROVIDE THE PRODUCT APPROVAL
 (MIAMI-DADE AND THE FLORIDA APPROVAL BOTH HAVE EFIS
 SYSTEMS UNDER THE PRODUCT APPROVAL SYSTEMS),
 MANUFACTURERS PRODUCT DATA FOR THE SYSTEM TO BE
 INSTALLED. PLEASE ALSO PROVIDE THE MANUFACTURERS
 INSTALLATION BROCHURE PROVIDING COMPLIANCE WITH 2014
 FBC-B SECTIONS;
 1408.2 PERFORMANCE CHARACTERISTICS.
 1408.2 PERFORMANCE CHARACTERISTICS.
 1408.3 STRUCTURAL DESIGN.
 1408.4 WEATHER RESISTANCE.
 1408.4.1 EIFS WITH DRAINAGE.
 408.4.1.1 WATER-RESISTIVE BARRIER.
 1408.5 INSTALLATION.
  
 17) PROVISO/ DEFERRED SUBMITTAL. 107 .3.4.2. PLEASE
 NOTE SHEET A 7.01 SHOWS A 3 PLY ROOF SYSTEM AND THE USE
 OF RIGID INSULATION BOARD OVER CORRUGATED METAL
 DECKING. PLEASE SUPPLY THE INSULATION PRODUCT APPROVAL,
 DEPENDING ON THE TYPE OF INSULATION BOARD INSTALLED
 ADDITIONAL MANUFACTURERS SPECIFICATION WILL PROVIDE THE
 VARIOUS WAYS THE INSULATION BOARD CAN BE VENTILATED.
 NOTE THE DESIGNER OF RECORD HAS NOT SPECIFIED WHAT TYPE
 OF VENTING WILL BE REQUIRED FOR THIS PROJECT, NOR IS
 THERE ANY SPEC LISTED UNDER THE STEEL DECK S1.1.
 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND
 DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 VENTING, FASTENING REQUIREMENTS, FLASHING REQUIREMENTS
 AND WIND RESISTANCE RATING THAT ARE REQUIRED TO BE
 INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL
 INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR
 THE SPECIFIC SITE.
  
 18) PROVISO/ DEFERRED SUBMITTAL. 107 .3.4.2. FOR ALL
 ROOFING PRODUCTS (PRODUCT APPROVALS) PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR
 BOTH INSULATION & THE BASE SHEET AS CALCULATED IN
 COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117.
 CALCULATION PREPARED, SIGNED AND SEALED BY A FLORIDA
 REGISTERED PROFESSIONAL ENGINEER OR REGISTERED
 ARCHITECT. 1609.6.4.4.1 COMPONENTS & CLADDING.
 19) PLEASE PROVIDE THE PRODUCT APPROVAL AND
 INSTALLATION INSTRUCTIONS FOR THE ROOF TOP LADDER. 2014
 FBC-B 1509.6.4 EQUIPMENT AND APPLIANCES ON ROOFS OR
 ELEVATED STRUCTURES.
  
 20) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 THE DESIGNER OF RECORD HAS SPOKEN WITH MR. SWOOPE AND
 MR. SWOOPE STATED THE IMPACT FEE ASSESSMENTS AND
 CREDITS WOULD FOLLOW THE FOLLOWING PLAN:
 PHASE 1- ASSESSMENT FOR IMPACT FEES FOR PHASE 1
 CONSTRUCTION.
 PHASE 2- CREDITS FOR THE DEMOLITION OF THE EXISTING VET
 OFFICE.
 PHASE 3- ASSESSMENT FOR RETAIL LESS CREDITS FOR THE
 EXISTING VET CLINIC EQUALS NET IMPACT FEES DUE FOR THE
 RETAIL.
  
 21) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  