| Date |
Text |
| 2018-03-06 13:21:42 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17050420 |
| | ADD: 5215 S. DIXIE HWY. |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: 561-523-1815 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 3RD REVIEW |
| | DATE: TUES. MARCH 06/2018 |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. UNITY OF TITLE FOR LOTS 5215, 5207 S. |
| | DIXIE AND 407 PUTNAM RD. |
| | |
| | 2) COMPLIED: . 108.3* BUILDING PERMIT VALUATION. |
| | FEE VALUE LOW. BASED ON THE CURRENT IIC TABLES FEB. 01/ |
| | 2017 THE VALUES ARE AS STATED: |
| | BUILDING IIB/ FIRE SPRINKLERED |
| | VET OFFICE 1097 SQ. FT. X $161.91= $177,615.00 |
| | MERCANTILE 4083 SQ. FT. X $117.10= $478,119.00 |
| | TOTAL DOLLAR AMOUNT $655,734.00 |
| | ADJUSTED VALUE FOR LISTED PERMITS BELOW $560,110.00. |
| | |
| | PLEASE DEDUCT THE FIRE SPRINKLER FOR BUILDING ONLY, AND |
| | FIRE ALARM FOR BUILDING AND ANY LOW VOLTAGE PERMIT FOR |
| | THE BUILDING. THE MECHANICAL, ELECTRIC, PLUMBING AND |
| | ROOFING ARE EACH $80.00 SUB-PERMITS WITH THEIR VALUE |
| | UNDER THE PRIME PERMIT. |
| | |
| | ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK |
| | STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE |
| | AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS & |
| | FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL |
| | TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED |
| | SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE, |
| | LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR |
| | FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE |
| | REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT. |
| | PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE |
| | ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE |
| | STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE |
| | REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE |
| | BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE |
| | BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR |
| | THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE |
| | PRIME OR MASTER PERMIT. |
| | |
| | 3A) PROVISO: ONCE THE NEW ANIMAL HOSPITAL IS COMPLETE, |
| | THE CONTRACTOR HAS TO REQUEST A TCO, (TEMPORARY |
| | CERTIFICATE OF OCCUPANCY). A FEE OF $500.00 DOLLARS IS |
| | INVOLVED AND IS GOOD FOR ONLY 90 DAYS. IF THE REMAINDER |
| | OF THE BUILDING IS NOT COMPLETE WITHIN 90 DAYS A 2ND |
| | REQUEST FOR TCO WILL NEED TO CONTINUE TO OCCUPY THE |
| | ANIMAL HOSPITAL AND AN ADDITIONAL FEE OF $500.00 WOULD |
| | BE REQUIRED. IF AFTER (2) CERTIFICATES THE BUILDING IS |
| | NOT COMPLETE, THE CONTRACTOR WILL THEN NEED TO APPLY TO |
| | THE BOARD OF ADJUSTMENT AND APPEAL FOR THE CONTINUATION |
| | OF THE TCO, FEES ASSOCIATED WITH THE BOARD OF |
| | ADJUSTMENT & APPEAL ARE $100.00. |
| | |
| | 3B)PROVISO: THE DESIGNER OF RECORD HAS SPOKEN WITH MR. |
| | SWOOPE AND MR. SWOOPE STATED THE IMPACT FEE ASSESSMENTS |
| | AND CREDITS WOULD FOLLOW THE FOLLOWING PLAN: |
| | PHASE 1- ASSESSMENT FOR IMPACT FEES FOR PHASE 1 |
| | CONSTRUCTION. |
| | PHASE 2- CREDITS FOR THE DEMOLITION OF THE EXISTING VET |
| | OFFICE. |
| | PHASE 3- ASSESSMENT FOR RETAIL LESS CREDITS FOR THE |
| | EXISTING VET CLINIC EQUALS NET IMPACT FEES DUE FOR THE |
| | RETAIL. |
| | |
| | 3C) 3RD REQUEST. 4X FEE / NOTICE!!!!! FLORIDA STATUTE |
| | 553.80(2)(B) . |
| | WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| | |
| | OF THE 3 SETS OF PLANS, THE ONE SET MARKED FOR |
| | ENGINEERING SHOWS THE NEW CORRECTED FS-1 PLAN. PLEASE |
| | NOTE ONLY ONE SET OF PLANS UPDATES WITH NEW FIRE |
| | SPRINKLER PLANS. THE THIRD ISSUE THAT WILL NEED TO BE |
| | CORRECTED IS FOUND ON THE FS-1 PLAN. AS DEPICTED THE |
| | FIRE LINE WILL NOT BE INSTALLED UNTIL THE PHASE III |
| | SINCE IT IS SHOWN GOING THROUGH THE SOUTH END OF THE |
| | BUILDING. THE FIRE SPRINKLER WILL NEED TO BE IN THE |
| | ANIMAL HOSPITAL IN PHASE ONE! THE PLAN NEEDS TO BE |
| | ROUTED IN A WAY THAT THE FIRE LINE ENTERS THE BUILDING |
| | AT PHASE ONE AND THEN IS EXTENDED IN PHASE III. |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 3D) 2ND REQUEST. THE SET MARKED FOR ENGINEERING IS |
| | MISSING THE COVERSHEET A0.00. |
| | |
| | 3E) 2ND REQUEST. THE SET MARKED FOR ENGINEERING IS |
| | MISSING A7.01 & A8.00 |
| | |
| | 3F) 2ND REQUEST. THE SET MARKED FOR ENGINEERING IS |
| | MISSING SHEET S3.3 IN ONE SET OF PLANS. |
| | |
| | 3G) 2ND REQUEST. THE 1 SET OF PLANS MARKED FOR |
| | ENGINEERING HAS C1-C6 DATED 09/28/17/ (2) SETS OF |
| | PLANS ARE MISSING THE CIVIL DRAWINGS C1-C6. |
| | |
| | 4-6) COMPLIED. |
| | |
| | 7) 2ND REQUEST. SHEET S2.1 UPPER RIGHT CORNER OF THE |
| | SHEET, NOTES INDICATE THE USE OF 5/8 INCH PERFORMANCE |
| | RATED PLYWOOD. SHEET S3.3 NOTES 5 & 8 BOTH INDICATE THE |
| | USE OF 5/8 INCH PLYWOOD. THE DESIGNER OF RECORD HAS |
| | DESIGNED THIS BUILDING TO BE CONSTRUCTION TYPE II-B. IN |
| | THE 2014 FBC-B SECTION 603.1.1.1.3 FIRE RETARDANT |
| | TREATED WOOD SHALL BE PERMITTED IN ROOF CONSTRUCTION |
| | INCLUDING, GIRDERS, TRUSSES, FRAMING, AND DECKING. |
| | PLEASE CORRECT THE PLANS, TO FIRE RETARDANT TREATED |
| | WOOD. |
| | |
| | DETAILS STILL SHOWING EITHER 5/8 INCH CDX PLYWOOD OR ? |
| | INCH PLYWOOD AND WOOD TRUSSES ON THE TOWERS: |
| | |
| | 7A) A5.01 DETAIL 3 5/8 INCH CDX PLYWOOD , WOOD OR METAL |
| | TRUSSES. |
| | |
| | 7B) SHEETS, A4.00 NOTE #9 , A4.01 NOTE # 9 & A5.00 NOTE |
| | # 9 ALL STATE ? INCH CDX PLYWOOD WITH EITHER WOOD OR |
| | METAL TRUSSES. |
| | |
| | 7C) SHEET S1.1 HEADING: PRE-ENGINEERED WOOD TRUSSES |
| | 7D) SHEET 52.1 NOTES ON PLYWOOD AT LIGHT GAUGE NOTES |
| | 5/8 INCH PLYWOOD. |
| | |
| | 7E) SHEET S2.2 HIGH ROOF FRAMING WOOD TRUSSES AND 5/8 |
| | INCH SHEATHING, NOTE 2 5/8 INCH WOOD SHEATHING |
| | |
| | 7F) SHEET S3.3 DETAIL 5, 8, & 9 ALL INDICATE THE USE OF |
| | PLYWOOD SHEATHING. SEE COMMENT (3F). |
| | |
| | 8) SEMI-COMPLIED. SHEET S2.1 THE BOTTOM TOWER (SOUTH) |
| | HAS A WALL SECTION DETAIL # 8/ S3.2. THE WALL SECTION |
| | ON THE OTHER SIDE OF THE TOWER DETAIL # 9/ S3.3, |
| | MISSING SHEET S3.3. DISCREPANCY IN PLANS. |
| | |
| | 8A) DETAIL 8/S3.2 IS THE ROOF TOP CURB NOT THE WALL |
| | SECTION ON THE BAR JOIST, PLEASE CORRECT. |
| | |
| | 8B) STILL MISSING THE S3.3 IN THE 3RD SET OF PLANS |
| | INDICATING ENGINEERING. . SEE COMMENT (3F). |
| | |
| | 9) 2ND REQUEST. SHEET A 5.01 DETAIL # 3 THE UPPER ROOF |
| | DETAIL INDICATES SHEATHING IS TO BE ATTACHED TO |
| | PRE-FABRICATED WOOD TRUSSES OR METAL ROOF TRUSSES REFER |
| | TO STRUCTURAL DRAWINGS. 2014 WEST PALM BEACH AMENDMENTS |
| | TO THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| | 107.2.1.3: W.P.B. ADMINISTRATIVE CODE/2014 DRAWINGS & |
| | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO |
| | THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR |
| | IN PART, OR, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE |
| | USED AS A SUBSTITUTE FOR SPECIFIC INFORMATION". |
| | |
| | 10-11) PROVISO/ DEFERRED SUBMITTAL. 107 .3.4.2. SHEET |
| | S3.2 SHOWS DETAIL # 8 THE CURB DETAIL FOR RTU SUPPORT. |
| | THE DETAIL DOES SHOW THE ATTACHMENT OF THE CURB TO THE |
| | ROOF FRAMING MEMBERS AND A MAXIMUM CURB HEIGHT OF 14 |
| | INCHES FROM THE FINISH ROOF DECK TO THE TOP OF THE |
| | CURB, THE DETAIL DOES NOT SHOW THE OVERLAP OF THE TOP |
| | OF THE RTU CURB, AS DETAILED ON M3. THE BOTTOM OF THE |
| | RTU UNIT (OVERLAP) HAS TO BE MOUNTED ON CURBS RAISED A |
| | MINIMUM OF 8 INCHES (203 MM) ABOVE THE ROOF SURFACE, OR |
| | WHERE ROOFING MATERIALS EXTEND BENEATH THE UNIT. FBC-B |
| | 1509.6.5 MECHANICAL UNITS. |
| | |
| | |
| | 12) 3RDND REQUEST. 4X FEE / NOTICE!!!!! FLORIDA STATUTE |
| | 553.80(2)(B) |
| | WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| | |
| | RESPONSE INDICATES REFER TO THE ATTACHED DENSEGLASS |
| | FLORIDA PRODUCT APPROVAL. |
| | SHEET A 5.00 NOTE 25 INDICATES THE USE OF 5/8 INCH |
| | DENSGLASS SHEATHING, PROVIDE A PRODUCT APPROVAL SHOWING |
| | THE TESTING AND TO WHAT DESIGN PRESSURES THE DENSGLASS |
| | CAN BE INSTALLED. 1609.6.4.4.1 COMPONENTS & CLADDING. |
| | RESPONSE INDICATES SEE ATTACHED DENSGLASS PRODUCT |
| | APPROVAL. THERE WERE NO PRODUCT APPROVALS AT ALL IN |
| | THIS SUBMISSION, THIS CAN BE A DEFERRED SUBMITTAL. |
| | |
| | 13) PROVISO/ DEFERRED SUBMITTAL. 107 .3.4.2. 2014 FBC-B |
| | 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 |
| | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| | AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 |
| | NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, FLAT AND SLOPED |
| | ROOFING, CURBS, ROOF TOP VENTILATORS |
| | |
| | 14) PROVISO/ DEFERRED SUBMITTAL. 107 .3.4.2. IDENTIFY |
| | GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE PRODUCT |
| | APPROVAL BEFORE SUBMITTING TO DESIGNER OF RECORD AND |
| | BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL |
| | PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE OPENING |
| | WIDTH & HEIGHT, TYPE OF GLAZING, MULLION INFORMATION IF |
| | REQUIRED, ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH |
| | OPENING SIZE. 2014 FBC-B 1405.13.1 INSTALLATION. |
| | WINDOWS AND DOORS SHALL BE INSTALLED IN ACCORDANCE WITH |
| | APPROVED MANUFACTURERS INSTRUCTIONS. FASTENER SIZE AND |
| | SPACING SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND |
| | SHALL BE CALCULATED BASED ON MAXIMUM LOADS AND SPACING |
| | USED IN THE TESTS. |
| | |
| | 15) PROVISO/ DEFERRED SUBMITTAL. 107 .3.4.2. FBC |
| | 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| | REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 |
| | (2) THE ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND |
| | REVIEWING ALL PROJECT DATA, REPORTS, SHOP DRAWINGS |
| | ETC.. |
| | |
| | 16) PROVISO/ DEFERRED SUBMITTAL. 107 .3.4.2. PROVISO/ |
| | DEFERRED SUBMITTAL. 107 .3.4.2. |
| | EFIS SYSTEMS: PLEASE PROVIDE THE PRODUCT APPROVAL |
| | (MIAMI-DADE AND THE FLORIDA APPROVAL BOTH HAVE EFIS |
| | SYSTEMS UNDER THE PRODUCT APPROVAL SYSTEMS), |
| | MANUFACTURERS PRODUCT DATA FOR THE SYSTEM TO BE |
| | INSTALLED. PLEASE ALSO PROVIDE THE MANUFACTURERS |
| | INSTALLATION BROCHURE PROVIDING COMPLIANCE WITH 2014 |
| | FBC-B SECTIONS; |
| | 1408.2 PERFORMANCE CHARACTERISTICS. |
| | 1408.2 PERFORMANCE CHARACTERISTICS. |
| | 1408.3 STRUCTURAL DESIGN. |
| | 1408.4 WEATHER RESISTANCE. |
| | 1408.4.1 EIFS WITH DRAINAGE. |
| | 408.4.1.1 WATER-RESISTIVE BARRIER. |
| | 1408.5 INSTALLATION. |
| | |
| | 17) PROVISO/ DEFERRED SUBMITTAL. 107 .3.4.2. PLEASE |
| | NOTE SHEET A 7.01 SHOWS A 3 PLY ROOF SYSTEM AND THE USE |
| | OF RIGID INSULATION BOARD OVER CORRUGATED METAL |
| | DECKING. PLEASE SUPPLY THE INSULATION PRODUCT APPROVAL, |
| | DEPENDING ON THE TYPE OF INSULATION BOARD INSTALLED |
| | ADDITIONAL MANUFACTURERS SPECIFICATION WILL PROVIDE THE |
| | VARIOUS WAYS THE INSULATION BOARD CAN BE VENTILATED. |
| | NOTE THE DESIGNER OF RECORD HAS NOT SPECIFIED WHAT TYPE |
| | OF VENTING WILL BE REQUIRED FOR THIS PROJECT, NOR IS |
| | THERE ANY SPEC LISTED UNDER THE STEEL DECK S1.1. |
| | 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE |
| | CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND |
| | DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS, |
| | VENTING, FASTENING REQUIREMENTS, FLASHING REQUIREMENTS |
| | AND WIND RESISTANCE RATING THAT ARE REQUIRED TO BE |
| | INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL |
| | INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR |
| | THE SPECIFIC SITE. |
| | |
| | 18) PROVISO/ DEFERRED SUBMITTAL. 107 .3.4.2. FOR ALL |
| | ROOFING PRODUCTS (PRODUCT APPROVALS) PLEASE IDENTIFY |
| | ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES |
| | FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL |
| | LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF |
| | ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR |
| | BOTH INSULATION & THE BASE SHEET AS CALCULATED IN |
| | COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117. |
| | CALCULATION PREPARED, SIGNED AND SEALED BY A FLORIDA |
| | REGISTERED PROFESSIONAL ENGINEER OR REGISTERED |
| | ARCHITECT. 1609.6.4.4.1 COMPONENTS & CLADDING. |
| | 19) PLEASE PROVIDE THE PRODUCT APPROVAL AND |
| | INSTALLATION INSTRUCTIONS FOR THE ROOF TOP LADDER. 2014 |
| | FBC-B 1509.6.4 EQUIPMENT AND APPLIANCES ON ROOFS OR |
| | ELEVATED STRUCTURES. |
| | |
| | 20) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | THE DESIGNER OF RECORD HAS SPOKEN WITH MR. SWOOPE AND |
| | MR. SWOOPE STATED THE IMPACT FEE ASSESSMENTS AND |
| | CREDITS WOULD FOLLOW THE FOLLOWING PLAN: |
| | PHASE 1- ASSESSMENT FOR IMPACT FEES FOR PHASE 1 |
| | CONSTRUCTION. |
| | PHASE 2- CREDITS FOR THE DEMOLITION OF THE EXISTING VET |
| | OFFICE. |
| | PHASE 3- ASSESSMENT FOR RETAIL LESS CREDITS FOR THE |
| | EXISTING VET CLINIC EQUALS NET IMPACT FEES DUE FOR THE |
| | RETAIL. |
| | |
| | 21) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. |
| | WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |