Plan Review Notes
Plan Review Notes For Permit 17050420
Permit Number 17050420
Review Stop R
Sequence Number 2
Notes
Date Text
2017-12-19 09:19:232014 FBC- BUILDING PLAN REVIEW/ ROOFING
 W. P. B. PERMIT: 17050420
 ADD: 5215 S. DIXIE HWY.
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-523-1815
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: TUES. DEC. 19/2017
 ACTION: BUILDING PROVISO
  
 1) PROVISO/ DEFERRED SUBMITTAL. 107 .3.4.2. 2014 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES, FLAT AND
 SLOPED ROOFING, CURBS, ROOF TOP VENTILATORS
  
 2) PROVISO/ DEFERRED SUBMITTAL. 107 .3.4.2. FBC
 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015
 (2) THE ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND
 REVIEWING ALL PROJECT DATA, REPORTS, SHOP DRAWINGS
 ETC..
  
 3) PROVISO/ DEFERRED SUBMITTAL. 107 .3.4.2. PLEASE NOTE
 SHEET A 7.01 SHOWS A 3 PLY ROOF SYSTEM AND THE USE OF
 RIGID INSULATION BOARD OVER CORRUGATED METAL DECKING.
 PLEASE SUPPLY THE INSULATION PRODUCT APPROVAL,
 DEPENDING ON THE TYPE OF INSULATION BOARD INSTALLED
 ADDITIONAL MANUFACTURERS SPECIFICATION WILL PROVIDE THE
 VARIOUS WAYS THE INSULATION BOARD CAN BE VENTILATED.
 NOTE THE DESIGNER OF RECORD HAS NOT SPECIFIED WHAT TYPE
 OF VENTING WILL BE REQUIRED FOR THIS PROJECT, NOR IS
 THERE ANY SPEC LISTED UNDER THE STEEL DECK S1.1.
 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND
 DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 VENTING, FASTENING REQUIREMENTS, FLASHING REQUIREMENTS
 AND WIND RESISTANCE RATING THAT ARE REQUIRED TO BE
 INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL
 INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR
 THE SPECIFIC SITE.
  
 4) PROVISO/ DEFERRED SUBMITTAL. 107 .3.4.2. FOR ALL
 ROOFING PRODUCTS (PRODUCT APPROVALS) PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR
 BOTH INSULATION & THE BASE SHEET AS CALCULATED IN
 COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117.
 CALCULATION PREPARED, SIGNED AND SEALED BY A FLORIDA
 REGISTERED PROFESSIONAL ENGINEER OR REGISTERED
 ARCHITECT. 1609.6.4.4.1 COMPONENTS & CLADDING.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  