Plan Review Notes
Plan Review Notes For Permit 17050420
Permit Number 17050420
Review Stop P
Sequence Number 2
Notes
Date Text
2018-01-02 13:27:141ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. ALL THE PLAN SHEETS ARE STAPLED TOGETHER AND OUT OF
 ORDER AND MISSING SHEETS PLEASE PROVIDE TWO SEPARATE
 AND COMPLETE PLAN SETS. PER WPB AMEND TO FBC 107.1
  
 2. SHT. A-2.00 THE NOTE ABOVE ENLARGED TOILET ROOM PLAN
 STATES ADA MOUNTING HEIGHTS DETAILS ON SHT. A-8.00 THAT
 PAGE IS MISSING FROM PLAN SET . PER WPB AMEND TO FBC
 107.1
  
 3. THE WATER HEATER DETAIL SHOWS TWO DIFFERENT SIZE
 WATER HEATERS A RHEEM EGSP30 AND ELDS52 PLEASE CLARIFY.
 PER WPB AMEND TO FBC 107.2.1
  
 4. PLEASE PLACE NOTE ON PLAN A SEPARATE PERMIT IS
 REQUIRED FOR BACK FLOW DEVISES. PER WPB UTILITIES
 DEPARTMENT
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  