| 2017-12-22 11:59:13 | 2ND REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17050420 |
| | 12/22/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE REVISED MECHANCIAL PLAN IS NOT IN COMPLIANCE. |
| | PLEASE SEE 1ST REVIEW COMMENT PRINTED BELOW: |
| | |
| | "MECHANICAL EXHAUST AT A RATE OF 0.90 CFMS PER SQUARE |
| | FOOT IS REQUIRED FOR ALL ANIMAL ROOMS OR SPACES OF THE |
| | PROPOSED ANIMAL HOSPITAL, AND RECIRCULATION OF AIR FROM |
| | THOSE ROOMS OR SPACES IS PROHIBITED- SEE TABLE 403.3 |
| | AND FOOTNOTE B. PLEASE CORRECT THE PLAN ACCORDINGLY." |
| | |
| | THE REVISED PLAN SHOWS A 300 CFM EXHAUST FAN IN THE LAB |
| | ROOM, HOWEVER IT IS NOT SIZED LARGE ENOUGH TO EXHAUST |
| | ALL ANIMAL AREAS OF THE OCCUPANCY, AND IS NOT LOCATED |
| | WHERE IT CAN ACTUALLY PROVIDE EXHAUST VENTILATION FOR |
| | ALL THE ANIMAL ROOMS AND AREAS. IN ADDITION, THE PLAN |
| | IS STILL INDICATING AIR FROM THE ANIMAL AREAS |
| | RECIRCULATING INTO THE WAITING ROOM, RECEPTION ROOM, |
| | CORRIDOR, AND |
| | |
| | RESTROOM WHICH IS PROHIBITED PER TABLE 403.3 FOOTNOTE |
| | B., AND SECTION 403.2.1 ITEM #3. "WHERE MECHANICAL |
| | EXHAUST IS REQUIRED BY NOTE B IN TABLE 403.3, |
| | RECIRCULATION OF AIR FROM SUCH SPACES SHALL BE |
| | PROHIBITED. ALL AIR SUPPLIED TO SUCH SPACES SHALL BE |
| | EXHAUSTED, INCLUDING ANY AIR IN EXCESS OF THAT REQUIRED |
| | BY TABLE 403.3. " |
| | |
| | PLEASE REVISE THE PLAN TO SHOW THE REQUIRED EXHAUST |
| | SYSTEM, AND INCLUDE BOTH AN EXHAUST VENTILATION |
| | CALCULATION AND AN AIR BALANCE CALCULATION. |
| | |
| | ADVISORY: DUE TO THE LARGE PERCENTAGE OF EXHAUST AND |
| | MAKEUP AIR REQUIRED FOR THE OCCUPANCY, AN ERV WILL MOST |
| | LIKELY BE REQUIRED. THE ENGINEER OF RECORD SHOULD |
| | REVIEW SECTION AND TABLE C403.2.6 FBC-14 ENERGY |
| | CONSERVATION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |