Plan Review Notes
Plan Review Notes For Permit 17050420
Permit Number 17050420
Review Stop M
Sequence Number 2
Notes
Date Text
2017-12-22 11:59:132ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17050420
 12/22/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE REVISED MECHANCIAL PLAN IS NOT IN COMPLIANCE.
 PLEASE SEE 1ST REVIEW COMMENT PRINTED BELOW:
  
 "MECHANICAL EXHAUST AT A RATE OF 0.90 CFMS PER SQUARE
 FOOT IS REQUIRED FOR ALL ANIMAL ROOMS OR SPACES OF THE
 PROPOSED ANIMAL HOSPITAL, AND RECIRCULATION OF AIR FROM
 THOSE ROOMS OR SPACES IS PROHIBITED- SEE TABLE 403.3
 AND FOOTNOTE B. PLEASE CORRECT THE PLAN ACCORDINGLY."
  
 THE REVISED PLAN SHOWS A 300 CFM EXHAUST FAN IN THE LAB
 ROOM, HOWEVER IT IS NOT SIZED LARGE ENOUGH TO EXHAUST
 ALL ANIMAL AREAS OF THE OCCUPANCY, AND IS NOT LOCATED
 WHERE IT CAN ACTUALLY PROVIDE EXHAUST VENTILATION FOR
 ALL THE ANIMAL ROOMS AND AREAS. IN ADDITION, THE PLAN
 IS STILL INDICATING AIR FROM THE ANIMAL AREAS
 RECIRCULATING INTO THE WAITING ROOM, RECEPTION ROOM,
 CORRIDOR, AND
  
 RESTROOM WHICH IS PROHIBITED PER TABLE 403.3 FOOTNOTE
 B., AND SECTION 403.2.1 ITEM #3. "WHERE MECHANICAL
 EXHAUST IS REQUIRED BY NOTE B IN TABLE 403.3,
 RECIRCULATION OF AIR FROM SUCH SPACES SHALL BE
 PROHIBITED. ALL AIR SUPPLIED TO SUCH SPACES SHALL BE
 EXHAUSTED, INCLUDING ANY AIR IN EXCESS OF THAT REQUIRED
 BY TABLE 403.3. "
  
 PLEASE REVISE THE PLAN TO SHOW THE REQUIRED EXHAUST
 SYSTEM, AND INCLUDE BOTH AN EXHAUST VENTILATION
 CALCULATION AND AN AIR BALANCE CALCULATION.
  
 ADVISORY: DUE TO THE LARGE PERCENTAGE OF EXHAUST AND
 MAKEUP AIR REQUIRED FOR THE OCCUPANCY, AN ERV WILL MOST
 LIKELY BE REQUIRED. THE ENGINEER OF RECORD SHOULD
 REVIEW SECTION AND TABLE C403.2.6 FBC-14 ENERGY
 CONSERVATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  