| 2017-12-04 13:50:07 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | PREVIOUS COMMENT # 3 IS RE-POSTED HERE FOR |
| | INFORMATIONAL PURPOSES: |
| | |
| | |
| | 3) SHEET A 1.00 - THERE IS AN INDICATION UNDER GENERAL |
| | LIFE SAFETY NOTES TO "REFER TO FIRE PROTECTION AND FIRE |
| | ALARM SHEETS FOR ADDITIONAL INFORMATION". I COULD NOT |
| | READILY IDENTIFY OR FIND ANY FIRE ALARM SHEETS. |
| | |
| | PLEASE PROVIDE PER THE COMMENT OR PROVIDE THE FOLLOWING |
| | NOTE OF COMPLAINCE. |
| | |
| | ALL FIRE ALARM WORK SHALL MEET THE REQUIRMENTS OF NFPA |
| | 72 AND SHALL BE UNDER SEPARATE SHOP DRAWINGS BY |
| | CERTIFIED LIFE SAFETY CONTRACTORS. |
| | |
| | |
| | |
| | PER NFPA 101 CHAPTER 9, BUILDING SERVICE AND FIRE |
| | PROTECTION EQUIPMENT |
| | |
| | 9.7.2.2 ALARM SIGNAL TRANSMISSION. WHERE SUPERVISION OF |
| | AUTOMATIC SPRINKLER SYSTEMS IS PROVIDED IN ACCORDANCE |
| | WITH ANOTHER PROVISION OF THIS CODE, WATERFLOW ALARMS |
| | SHALL BE TRANSMITTED TO AN APPROVED, PROPRIETARY |
| | ALARM-RECEIVING FACILITY, A REMOTE STATION, A CENTRAL |
| | STATION, OR THE FIRE DEPARTMENT. SUCH CONNECTION SHALL |
| | BE IN ACCORDANCE WITH 9.6.1.3. |
| | |
| | |
| | A FIRE ALARM SYSTEM COMPLYING WITH THE ABOVE CODE SHALL |
| | BE INSTALLED. |
| | |
| | |
| | NEW COMMENT |
| | |
| | 1) THE REVISED SHEETS APPEAR TO ALL STAPLED TOGETHER |
| | AND IN RANDOM ORDER. THEY HAVE NOT BEEN PROPERLY |
| | INSERTED INTO THE ORIGINAL SET. IT IS UCLEAR WHAT THE |
| | FINAL SET IS OR WHAT IS REPRESENTED OF THE OFFICIAL |
| | FINAL SET. |
| | |
| | PLEASE CORRECT OR JUSTIFY |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |