Plan Review Notes For Permit 17050420
Permit Number 17050420
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2017-12-04 13:50:07THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 PREVIOUS COMMENT # 3 IS RE-POSTED HERE FOR
 INFORMATIONAL PURPOSES:
  
  
 3) SHEET A 1.00 - THERE IS AN INDICATION UNDER GENERAL
 LIFE SAFETY NOTES TO "REFER TO FIRE PROTECTION AND FIRE
 ALARM SHEETS FOR ADDITIONAL INFORMATION". I COULD NOT
 READILY IDENTIFY OR FIND ANY FIRE ALARM SHEETS.
  
 PLEASE PROVIDE PER THE COMMENT OR PROVIDE THE FOLLOWING
 NOTE OF COMPLAINCE.
  
 ALL FIRE ALARM WORK SHALL MEET THE REQUIRMENTS OF NFPA
 72 AND SHALL BE UNDER SEPARATE SHOP DRAWINGS BY
 CERTIFIED LIFE SAFETY CONTRACTORS.
  
  
  
 PER NFPA 101 CHAPTER 9, BUILDING SERVICE AND FIRE
 PROTECTION EQUIPMENT
  
 9.7.2.2 ALARM SIGNAL TRANSMISSION. WHERE SUPERVISION OF
 AUTOMATIC SPRINKLER SYSTEMS IS PROVIDED IN ACCORDANCE
 WITH ANOTHER PROVISION OF THIS CODE, WATERFLOW ALARMS
 SHALL BE TRANSMITTED TO AN APPROVED, PROPRIETARY
 ALARM-RECEIVING FACILITY, A REMOTE STATION, A CENTRAL
 STATION, OR THE FIRE DEPARTMENT. SUCH CONNECTION SHALL
 BE IN ACCORDANCE WITH 9.6.1.3.
  
  
 A FIRE ALARM SYSTEM COMPLYING WITH THE ABOVE CODE SHALL
 BE INSTALLED.
  
  
 NEW COMMENT
  
 1) THE REVISED SHEETS APPEAR TO ALL STAPLED TOGETHER
 AND IN RANDOM ORDER. THEY HAVE NOT BEEN PROPERLY
 INSERTED INTO THE ORIGINAL SET. IT IS UCLEAR WHAT THE
 FINAL SET IS OR WHAT IS REPRESENTED OF THE OFFICIAL
 FINAL SET.
  
 PLEASE CORRECT OR JUSTIFY
  
  
 PETER LEDUC
 FIRE MARSHAL