2017-08-09 08:30:022014 FBC-ROOFING/ BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17050420
 ADD: 5215 S. DIXIE HWY.
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-523-1815
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: TUES. AUGUST 08/2017
 ACTION: DENIED
  
  
 1) MISSING: 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (D) ROOFING PRODUCTS AND ASSEMBLIES, FLAT AND SLOPED
 ROOFING, CURBS, ROOF TOP VENTILATORS
  
 2) PLEASE NOTE SHEET A 7.01 SHOWS A 3 PLY ROOF SYSTEM
 AND THE USE OF RIGID INSULATION BOARD OVER CORRUGATED
 METAL DECKING. PLEASE SUPPLY THE INSULATION PRODUCT
 APPROVAL, DEPENDING ON THE TYPE OF INSULATION BOARD
 INSTALLED ADDITIONAL MANUFACTURERS SPECIFICATION WILL
 PROVIDE THE VARIOUS WAYS THE INSULATION BOARD CAN BE
 VENTILATED. NOTE THE DESIGNER OF RECORD HAS NOT
 SPECIFIED WHAT TYPE OF VENTING WILL BE REQUIRED FOR
 THIS PROJECT, NOR IS THERE ANY SPEC LISTED UNDER THE
 STEEL DECK S1.1.
 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND
 DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 VENTING, FASTENING REQUIREMENTS, FLASHING REQUIREMENTS
 AND WIND RESISTANCE RATING THAT ARE REQUIRED TO BE
 INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL
 INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR
 THE SPECIFIC SITE.
  
 3) FOR ALL ROOFING PRODUCTS (PRODUCT APPROVALS) PLEASE
 IDENTIFY ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED
 PRESSURES FOR ROOF ZONE # 1. REVIEW THE PRODUCT
 APPROVAL LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED
 FOR ROOF ZONES 2 & 3. FASTENER DENSITIES SHALL BE
 INCREASED FOR BOTH INSULATION & THE BASE SHEET AS
 CALCULATED IN COMPLIANCE WITH ROOFING APPLICATION
 STANDARDS RAS 117. CALCULATION PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER