| 2017-08-09 08:30:02 | 2014 FBC-ROOFING/ BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17050420 |
| | ADD: 5215 S. DIXIE HWY. |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: 561-523-1815 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | DATE: TUES. AUGUST 08/2017 |
| | ACTION: DENIED |
| | |
| | |
| | 1) MISSING: 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, FLAT AND SLOPED |
| | ROOFING, CURBS, ROOF TOP VENTILATORS |
| | |
| | 2) PLEASE NOTE SHEET A 7.01 SHOWS A 3 PLY ROOF SYSTEM |
| | AND THE USE OF RIGID INSULATION BOARD OVER CORRUGATED |
| | METAL DECKING. PLEASE SUPPLY THE INSULATION PRODUCT |
| | APPROVAL, DEPENDING ON THE TYPE OF INSULATION BOARD |
| | INSTALLED ADDITIONAL MANUFACTURERS SPECIFICATION WILL |
| | PROVIDE THE VARIOUS WAYS THE INSULATION BOARD CAN BE |
| | VENTILATED. NOTE THE DESIGNER OF RECORD HAS NOT |
| | SPECIFIED WHAT TYPE OF VENTING WILL BE REQUIRED FOR |
| | THIS PROJECT, NOR IS THERE ANY SPEC LISTED UNDER THE |
| | STEEL DECK S1.1. |
| | 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE |
| | CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND |
| | DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS, |
| | VENTING, FASTENING REQUIREMENTS, FLASHING REQUIREMENTS |
| | AND WIND RESISTANCE RATING THAT ARE REQUIRED TO BE |
| | INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL |
| | INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR |
| | THE SPECIFIC SITE. |
| | |
| | 3) FOR ALL ROOFING PRODUCTS (PRODUCT APPROVALS) PLEASE |
| | IDENTIFY ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED |
| | PRESSURES FOR ROOF ZONE # 1. REVIEW THE PRODUCT |
| | APPROVAL LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED |
| | FOR ROOF ZONES 2 & 3. FASTENER DENSITIES SHALL BE |
| | INCREASED FOR BOTH INSULATION & THE BASE SHEET AS |
| | CALCULATED IN COMPLIANCE WITH ROOFING APPLICATION |
| | STANDARDS RAS 117. CALCULATION PREPARED, SIGNED AND |
| | SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR |
| | REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. |
| | |