| 2017-08-24 11:24:58 | 1ST REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. A MIN OF ONE OF THE EXAM ROOM SINKS SHALL COMPLY |
| | WITH FBC ACC 606 PER FBC ACC 212.3 |
| | |
| | 2. TEMPERED WATER IS REQUIRED AT LAVATORY. PER FBC PL |
| | 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING |
| | FACILITIES. |
| | TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND |
| | GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES |
| | PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED |
| | WATER SHALL BE DELIVERED THROUGH AN APPROVED |
| | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| | 1070 OR CSA B125.3. |
| | |
| | 3. IN THE FIXTURE SCHEDULE A P4H DRINKING FOUNTAIN IS |
| | SHOWN BUT THERE IS NOT ONE SHOWN ON THE FLOOR PLAN OR |
| | RISER PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 4. A LENT TRAP IS REQUIRED ON WASHING MACHINE. PER FBC |
| | PL 1003.6 LAUNDRIES. |
| | LAUNDRY FACILITIES NOT INSTALLED WITHIN AN INDIVIDUAL |
| | DWELLING UNIT OR INTENDED FOR INDIVIDUAL FAMILY USE |
| | SHALL BE EQUIPPED WITH AN INTERCEPTOR WITH A WIRE |
| | BASKET OR SIMILAR DEVICE, REMOVABLE FOR CLEANING, THAT |
| | PREVENTS PASSAGE INTO THE DRAINAGE SYSTEM OF SOLIDS 1/2 |
| | INCH (12.7 MM) OR LARGER IN SIZE, STRING, RAGS, BUTTONS |
| | OR OTHER MATERIALS DETRIMENTAL TO THE PUBLIC SEWAGE |
| | SYSTEM. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |