| Notes |
| Date |
Text |
| 2017-08-24 13:33:54 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17050420 | | | 8/25/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) MECHANICAL EXHAUST AT A RATE OF 0.90 CFMS PER SQUARE | | | FOOT IS REQUIRED FOR ALL ANIMAL ROOMS OR SPACES OF THE | | | PROPOSED ANIMAL HOSPITAL, AND RECIRCULATION OF AIR FROM | | | THOSE ROOMS OR SPACES IS PROHIBITED- SEE TABLE 403.3 | | | AND FOOTNOTE B. PLEASE CORRECT THE PLAN ACCORDINGLY. | | | | | | 2) M-3: PROVIDE THE WIND LOAD DESIGN CRITERIA AND | | | COMPLETE ENGINEERING FOR INSTALLATION OF THE NEW RTU. | | | MISSING FROM THE DETAIL ARE: LENGTH DIMENSIONS OF THE | | | HURRICANE STRAPS, NUMBER OF STRAPS TO BE INSTALLED AND | | | PLACEMENT OF THE STRAPS, PLACEMENT OF THE L-ANGLES; AND | | | FOR THE CURB TO ROOF STRUCTURE ATTACHEMENT- TYPE AND | | | SIZE OF ANCHORS, AND NUMBER AND PLACEMENT OF ANCHORS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|