| 2017-07-27 14:47:00 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) SHEET 1.00 THERE ARE NO INDICATIONS OF REVEIW AND/OR |
| | COMPLIANCE WITH ANY FIRE CODE. |
| | |
| | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| | 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING |
| | THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| | APPLICABLE CODES OR STANDARDS. |
| | |
| | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 13, 2010 EDITION. |
| | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 72, 2010 EDITION. |
| | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 241, 2009 EDITION. |
| | FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 10, 2010 EDITION. |
| | ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION. |
| | |
| | |
| | PLEASE PROVIDE AN APPLICABLE NOTE OF REVIEW AND |
| | COMPLAINCE. |
| | |
| | |
| | |
| | 3) SHEET A 1.00 - THERE IS AN INDICATION UNDER GENERAL |
| | LIFE SAFETY NOTES TO "REFER TO FIRE PROTECTION AND FIRE |
| | ALARM SHEETS FOR ADDITIONAL INFORMATION". I COULD NOT |
| | READILY IDENTIFY OR FIND ANY FIRE ALARM SHEETS. |
| | |
| | PLEASE PROVIDE PER THE COMMENT OR PROVIDE THE FOLLOWING |
| | NOTE OF COMPLAINCE. |
| | |
| | ALL FIRE ALARM WORK SHALL MEET THE REQUIRMENTS OF NFPA |
| | 72 AND SHALL BE UNDER SEPARATE SHOP DRAWINGS BY |
| | CERTIFIED LIFE SAFETY CONTRACTORS. |
| | |
| | |
| | |
| | 4) SHEET A 4.00 - THE ROOF TRUSS ARE OF LIGHTWEIGHT |
| | TRUSS DESIGN. |
| | |
| | PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED FOR |
| | STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE CONSTRUCTION. |
| | ANY COMMERCIAL, INDUSTRIAL, OR ANY MULTIUNIT |
| | RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE WHICH USES |
| | HORIZONTAL OR VERTICAL LIGHT-FRAME TRUSS-TYPE |
| | CONSTRUCTION IN ANY PORTION SHALL BE MARKED WITH A |
| | MALTESE CROSS SIGN MEASURING 8 INCHES HORIZONTALLY AND |
| | 8 INCHES VERTICALLY, OF A BRIGHT RED REFLECTIVE COLOR. |
| | THE APPROVED SYMBOL SHALL BE PLACED WITHIN 24 INCHES TO |
| | THE LEFT OF THE MAIN ENTRY DOOR. |
| | 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE |
| | MARKED WITH THE LETTER "R". |
| | 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS |
| | SHALL BE MARKED WITH THE LETTER "F". |
| | 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF |
| | SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F". |
| | |
| | |
| | PLEASE PROVIDE AN APPLICABLE NOTE OF COMPLIANCE. |
| | |
| | |
| | |
| | 5) SHEET 6.00 - THE DOOR SCHEDULE INDICATES HARDWARE |
| | AND LOCKS/DEAD BOLTS ON THE EXIT DOORS. |
| | |
| | ALL EXIT HARWARE SHALL COMPLY WITH NFPA 101, CHAPTER 7, |
| | MEANS OF EGRESS. |
| | |
| | PER CHAPTER 38, NEW BUSINESS |
| | 38.2.2.2 DOORS. |
| | 38.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE |
| | PERMITTED. |
| | 38.2.2.2.2* LOCKS COMPLYING WITH 7.2.1.5.5 SHALL BE |
| | PERMITTED ONLY ON PRINCIPAL ENTRANCE/EXIT DOORS. |
| | |
| | PER CHAPTER, 36, NEW MERCANTILE |
| | 36.2.2.2 DOORS. |
| | 36.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE |
| | PERMITTED. |
| | 36.2.2.2.2* LOCKS COMPLYING WITH 7.2.1.5.5 SHALL BE |
| | PERMITTED ONLY ON PRINCIPAL ENTRANCE/EXIT DOORS. |
| | |
| | 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. |
| | 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED |
| | READILY FROM THE EGRESS SIDE WHENEVER THE BUILDING IS |
| | OCCUPIED. |
| | 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY |
| | TO DOOR LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER |
| | EXPOSURE TO ELEVATED TEMPERATURE IN ACCORDANCE WITH THE |
| | LISTING, BASED ON LABORATORY FIRE TEST PROCEDURES. |
| | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE |
| | OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR |
| | OPERATION FROM THE EGRESS SIDE. |
| | |
| | 7.2.1.5.5.1 EXTERIOR DOOR ASSEMBLIES SHALL BE PERMITTED |
| | TO HAVE KEYOPERATED LOCKS FROM THE EGRESS SIDE, |
| | PROVIDED THAT ALL OF THE FOLLOWING CRITERIA ARE MET: |
| | (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11 |
| | THROUGH 43 FOR THE SPECIFIC OCCUPANCY. |
| | (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS |
| | THAN 1 IN. (25 MM) HIGH ON A CONTRASTING BACKGROUND |
| | THAT READS AS FOLLOWS IS LOCATED ON OR ADJACENT TO THE |
| | DOOR LEAF: THIS DOOR TO REMAIN UNLOCKED WHEN THE |
| | BUILDING IS |
| | OCCUPIED. |
| | (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY |
| | DISTINGUISHABLE AS LOCKED. |
| | (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT |
| | INSIDE THE BUILDING WHEN IT IS LOCKED. 7.2.1.5.5.2 THE |
| | ALTERNATIVE PROVISIONS OF 7.2.1.5.5.1 SHALL BE |
| | PERMITTED TO BE REVOKED BY THE AUTHORITY HAVING |
| | JURISDICTION FOR CAUSE. |
| | |
| | PLEASE PROVIDE AN APPLICABLE NOTE OF SPEC SHEETS THAT |
| | WILL INDICATE COMPLIANCE WITH THE REQUIRMENTS. |
| | |
| | |
| | |
| | |
| | 6) SHEET E 1 - THIS IS RELATED TO # 3 ABOVE. THERE ARE |
| | NO INDICATIONS ON THE ELECTRICAL PLAN SHEETS OF A FIRE |
| | ALARM SYSTEM OR EQUIPMENT. |
| | |
| | ALL FIRE ALARM WORK SHALL MEET THE REQUIRMENTS OF NFPA |
| | 72 AND SHALL BE UNDER SEPARATE SHOP DRAWINGS BY |
| | CERTIFIED LIFE SAFETY CONTRACTORS. |
| | |
| | PLEASE PROVIDE A NOTE OF COMPLAINCE. |
| | |
| | |
| | |
| | |
| | 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | |
| | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |