Plan Review Notes
Plan Review Notes For Permit 17050420
Permit Number 17050420
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-07-27 14:47:00THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET 1.00 THERE ARE NO INDICATIONS OF REVEIW AND/OR
 COMPLIANCE WITH ANY FIRE CODE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
  
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF REVIEW AND
 COMPLAINCE.
  
  
  
 3) SHEET A 1.00 - THERE IS AN INDICATION UNDER GENERAL
 LIFE SAFETY NOTES TO "REFER TO FIRE PROTECTION AND FIRE
 ALARM SHEETS FOR ADDITIONAL INFORMATION". I COULD NOT
 READILY IDENTIFY OR FIND ANY FIRE ALARM SHEETS.
  
 PLEASE PROVIDE PER THE COMMENT OR PROVIDE THE FOLLOWING
 NOTE OF COMPLAINCE.
  
 ALL FIRE ALARM WORK SHALL MEET THE REQUIRMENTS OF NFPA
 72 AND SHALL BE UNDER SEPARATE SHOP DRAWINGS BY
 CERTIFIED LIFE SAFETY CONTRACTORS.
  
  
  
 4) SHEET A 4.00 - THE ROOF TRUSS ARE OF LIGHTWEIGHT
 TRUSS DESIGN.
  
 PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED FOR
 STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE CONSTRUCTION.
 ANY COMMERCIAL, INDUSTRIAL, OR ANY MULTIUNIT
 RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE WHICH USES
 HORIZONTAL OR VERTICAL LIGHT-FRAME TRUSS-TYPE
 CONSTRUCTION IN ANY PORTION SHALL BE MARKED WITH A
 MALTESE CROSS SIGN MEASURING 8 INCHES HORIZONTALLY AND
 8 INCHES VERTICALLY, OF A BRIGHT RED REFLECTIVE COLOR.
 THE APPROVED SYMBOL SHALL BE PLACED WITHIN 24 INCHES TO
 THE LEFT OF THE MAIN ENTRY DOOR.
 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE
 MARKED WITH THE LETTER "R".
 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS
 SHALL BE MARKED WITH THE LETTER "F".
 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF
 SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F".
  
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF COMPLIANCE.
  
  
  
 5) SHEET 6.00 - THE DOOR SCHEDULE INDICATES HARDWARE
 AND LOCKS/DEAD BOLTS ON THE EXIT DOORS.
  
 ALL EXIT HARWARE SHALL COMPLY WITH NFPA 101, CHAPTER 7,
 MEANS OF EGRESS.
  
 PER CHAPTER 38, NEW BUSINESS
 38.2.2.2 DOORS.
 38.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
 38.2.2.2.2* LOCKS COMPLYING WITH 7.2.1.5.5 SHALL BE
 PERMITTED ONLY ON PRINCIPAL ENTRANCE/EXIT DOORS.
  
 PER CHAPTER, 36, NEW MERCANTILE
 36.2.2.2 DOORS.
 36.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
 36.2.2.2.2* LOCKS COMPLYING WITH 7.2.1.5.5 SHALL BE
 PERMITTED ONLY ON PRINCIPAL ENTRANCE/EXIT DOORS.
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM THE EGRESS SIDE WHENEVER THE BUILDING IS
 OCCUPIED.
 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY
 TO DOOR LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER
 EXPOSURE TO ELEVATED TEMPERATURE IN ACCORDANCE WITH THE
 LISTING, BASED ON LABORATORY FIRE TEST PROCEDURES.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR
 OPERATION FROM THE EGRESS SIDE.
  
 7.2.1.5.5.1 EXTERIOR DOOR ASSEMBLIES SHALL BE PERMITTED
 TO HAVE KEYOPERATED LOCKS FROM THE EGRESS SIDE,
 PROVIDED THAT ALL OF THE FOLLOWING CRITERIA ARE MET:
 (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11
 THROUGH 43 FOR THE SPECIFIC OCCUPANCY.
 (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN. (25 MM) HIGH ON A CONTRASTING BACKGROUND
 THAT READS AS FOLLOWS IS LOCATED ON OR ADJACENT TO THE
 DOOR LEAF: THIS DOOR TO REMAIN UNLOCKED WHEN THE
 BUILDING IS
 OCCUPIED.
 (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY
 DISTINGUISHABLE AS LOCKED.
 (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT
 INSIDE THE BUILDING WHEN IT IS LOCKED. 7.2.1.5.5.2 THE
 ALTERNATIVE PROVISIONS OF 7.2.1.5.5.1 SHALL BE
 PERMITTED TO BE REVOKED BY THE AUTHORITY HAVING
 JURISDICTION FOR CAUSE.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF SPEC SHEETS THAT
 WILL INDICATE COMPLIANCE WITH THE REQUIRMENTS.
  
  
  
  
 6) SHEET E 1 - THIS IS RELATED TO # 3 ABOVE. THERE ARE
 NO INDICATIONS ON THE ELECTRICAL PLAN SHEETS OF A FIRE
 ALARM SYSTEM OR EQUIPMENT.
  
 ALL FIRE ALARM WORK SHALL MEET THE REQUIRMENTS OF NFPA
 72 AND SHALL BE UNDER SEPARATE SHOP DRAWINGS BY
 CERTIFIED LIFE SAFETY CONTRACTORS.
  
 PLEASE PROVIDE A NOTE OF COMPLAINCE.
  
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  