2017-08-17 13:34:29CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE AIC RATING OF THE SERVICE
 EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. NEC 110.9,
 110.10
 2. PROVIDE AIC RATING OF SERVICE EQUIPMENT AND PANELS.
 NEC 110.3, 110.9
 3. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 4. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. NEC 250.94
 5. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. AN ESTIMATE FOR RETAIL SPACES BASED ON SQUARE
 FOOTAGE WILL BE ACCEPTABLE IF USE IS NOT DETERMINED.
 NEC 220
 6. PROVIDE AUTOMATIC CONTROL FOR SHOW WINDOW OUTLETS
 PER ENERGY CODE. FBC C405.2.3
 7. PROVIDE INTERIOR LIGHTING CALCULATION SHOWING
 COMPLIANCE WITH THE FBC ENERGY CODE FOR EACH SPACE. FBC
 C405.5
 8. PANEL A SHOWS THE WATER HEATER BREAKER SIZED AT 30
 AMPS, WHICH IS TOO LARGE. BREAKER SHOULD BE SIZED AT
 125% OF LOAD. PROVIDE CORRECTION. NEC 422.13
 9. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED
 IN THE FBC ENERGY CODE FOR THE RETAIL BAYS. FBC
 C405.2.2, 405.2.2.2
 10. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED
 IN THE FBC ENERGY CODE FOR THE COVERED PATIO AREA. FBC
 C405.2.4
 11. NAME OF PANELS ON POWER PLAN IS DIFFERENT THAN
 PANEL SCHEDULES AND RISER DIAGRAM. PROVIDE CORRECTION.
 FBC 107.2.1
 12. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED
 SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR ALL LOW VOLTAGE SYSTEMS TO INCLUDE BUT
 NOT LIMITED TO FIRE ALARM, CCTV, PHONE AND DATA,
 WIRELESS SYSTEMS, ETC. FBC 105.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  