| 2017-08-17 13:34:29 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE AIC RATING OF THE SERVICE |
| | EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. NEC 110.9, |
| | 110.10 |
| | 2. PROVIDE AIC RATING OF SERVICE EQUIPMENT AND PANELS. |
| | NEC 110.3, 110.9 |
| | 3. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF |
| | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND |
| | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 |
| | 4. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. NEC 250.94 |
| | 5. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL |
| | LOADS. AN ESTIMATE FOR RETAIL SPACES BASED ON SQUARE |
| | FOOTAGE WILL BE ACCEPTABLE IF USE IS NOT DETERMINED. |
| | NEC 220 |
| | 6. PROVIDE AUTOMATIC CONTROL FOR SHOW WINDOW OUTLETS |
| | PER ENERGY CODE. FBC C405.2.3 |
| | 7. PROVIDE INTERIOR LIGHTING CALCULATION SHOWING |
| | COMPLIANCE WITH THE FBC ENERGY CODE FOR EACH SPACE. FBC |
| | C405.5 |
| | 8. PANEL A SHOWS THE WATER HEATER BREAKER SIZED AT 30 |
| | AMPS, WHICH IS TOO LARGE. BREAKER SHOULD BE SIZED AT |
| | 125% OF LOAD. PROVIDE CORRECTION. NEC 422.13 |
| | 9. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED |
| | IN THE FBC ENERGY CODE FOR THE RETAIL BAYS. FBC |
| | C405.2.2, 405.2.2.2 |
| | 10. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED |
| | IN THE FBC ENERGY CODE FOR THE COVERED PATIO AREA. FBC |
| | C405.2.4 |
| | 11. NAME OF PANELS ON POWER PLAN IS DIFFERENT THAN |
| | PANEL SCHEDULES AND RISER DIAGRAM. PROVIDE CORRECTION. |
| | FBC 107.2.1 |
| | 12. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED |
| | SEPARATE PERMITS AND DATA SPECIFICATION SHEET |
| | SUBMITTALS FOR ALL LOW VOLTAGE SYSTEMS TO INCLUDE BUT |
| | NOT LIMITED TO FIRE ALARM, CCTV, PHONE AND DATA, |
| | WIRELESS SYSTEMS, ETC. FBC 105.1 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |
| | |