Plan Review Notes
Plan Review Notes For Permit 17050420
Permit Number 17050420
Review Stop B
Sequence Number 1
Notes
Date Text
2017-08-09 08:26:102014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17050420
 ADD: 5215 S. DIXIE HWY.
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-523-1815
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: TUES. AUGUST 08/2017
 ACTION: DENIED
  
 1) THE PLANS INDICATE THAT THERE IS A UNITY OF TITLE
 FOR LOTS 5215, 5207 S. DIXIE AND 407 PUTNAM RD. THE
 PERMIT APPLICATION ALSO STATES THAT THERE IS A UNITY OF
 TITLE ON FILE. A RECORDED COPY OF THE UNITY OF TITLE
 NEEDS TO BE SUBMITTED WITH THIS PLAN TO SHOW PROOF THAT
 THE BUILDING DOES NOT TRANSGRESS PROPERTY LINES.
 2014 FBC-B TABLE 602.
  
 2) 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 WITH REGIONAL ADJUSTMENTS FOR LOCATION AS PUBLISHED BY
 THE INTERNATIONAL CODE CONGRESS.
  
 FEE VALUE LOW. BASED ON THE CURRENT IIC TABLES FEB. 01/
 2017 THE VALUES ARE AS STATED:
 BUILDING IIB/ FIRE SPRINKLERED
 VET OFFICE 1097 SQ. FT. X $161.91= $177,615.00
 MERCANTILE 4083 SQ. FT. X $117.10= $478,119.00
 TOTAL DOLLAR AMOUNT $655,734.00
  
 PLEASE DEDUCT THE FIRE SPRINKLER FOR BUILDING ONLY, AND
 FIRE ALARM FOR BUILDING AND ANY LOW VOLTAGE PERMIT FOR
 THE BUILDING. THE MECHANICAL, ELECTRIC, PLUMBING AND
 ROOFING ARE EACH $80.00 SUB-PERMITS WITH THEIR VALUE
 UNDER THE PRIME PERMIT.
  
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK
 STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE,
 LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE
 BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR
 THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE
 PRIME OR MASTER PERMIT.
  
 3) PLEASE BE AWARE OF PROBLEMS INVOLVED WITH THE PHASED
 PERMITTING;
 3A) ONCE THE NEW ANIMAL HOSPITAL IS COMPLETE, THE
 CONTRACTOR HAS TO REQUEST A TCO, (TEMPORARY CERTIFICATE
 OF OCCUPANCY). A FEE OF $500.00 DOLLARS IS INVOLVED AND
 IS GOOD FOR ONLY 90 DAYS. IF THE REMAINDER OF THE
 BUILDING IS NOT COMPLETE WITHIN 90 DAYS A 2ND REQUEST
 FOR TCO WILL NEED TO CONTINUE TO OCCUPY THE ANIMAL
 HOSPITAL AND AN ADDITIONAL FEE OF $500.00 WOULD BE
 REQUIRED. IF AFTER (2) CERTIFICATES THE BUILDING IS NOT
 COMPLETE, THE CONTRACTOR WILL THEN NEED TO APPLY TO THE
 BOARD OF ADJUSTMENT AND APPEAL FOR THE CONTINUATION OF
 THE TCO, FEES ASSOCIATED WITH THE BOARD OF ADJUSTMENT &
 APPEAL ARE $100.00.
  
 3B) A SECOND ISSUE IS HOW THE COUNTY IMPACT FEES ARE TO
 BE PAID FOR THE WHOLE BUILDING BEFORE THE DEMOLITION OF
 THE EXISTING BUILDING AND CREDITS THAT WOULD BE DUE.
 THE CONTRACTOR OR OWNER WILL NEED TO DISCUSS THIS WITH
 MR. SWOOP 561-233-2014 AT PALM BEACH COUNTY IMPACT FEE
 OFFICE.
  
 3C) THE THIRD ISSUE THAT WILL NEED TO BE CORRECTED IS
 FOUND ON THE FS-1 PLAN. AS DEPICTED THE FIRE LINE WILL
 NOT BE INSTALLED UNTIL THE PHASE III SINCE IT IS SHOWN
 GOING THROUGH THE SOUTH END OF THE BUILDING. THE FIRE
 SPRINKLER WILL NEED TO BE IN THE ANIMAL HOSPITAL IN
 PHASE ONE! THE PLAN NEEDS TO BE ROUTED IN A WAY THAT
 THE FIRE LINE ENTERS THE BUILDING AT PHASE ONE AND THEN
 IS EXTENDED IN PHASE III. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 4) SHEET A 1.00 THE LIFE SAFETY PLAN:
 4A) GENERAL LIFE SAFETY PLAN NOTE # 4 INDICATES THE
 MAXIMUM ELEVATION CHANGE AT ALL BUILDING ENTRANCE DOORS
 (INCLUDING THRESHOLDS) AND ALONG THE REQUIRED MEANS OF
 EGRESS SHALL BE EQUAL TO OR LESS THAN ? INCH. THE LIFE
 SAFETY PLAN DOES NOT PROVIDE EXIT SIGNS DIRECTING WHICH
 DOOR IS THE REQUIRED MEANS OF EGRESS. SHEET E2 SHOWS
 EXIT LIGHT AND BATTERY BACKUP LIGHTS OVER BOTH EXITS.
 THE COMMON PATH OF TRAVEL IS NOT EXCEEDED (75 FEET
 LIMIT). WHEN YOU GO TO THE C-1 SHEET SHOWS AT THE
 ANIMAL HOSPITAL, BAY # 1 AND BAY # 2 APPROXIMATELY A
 CHANGE IN GRADE FROM THE LANDING TO THE CITY SIDEWALK.
 THE ELEVATION TAGS ON SHEET C1 SHOW A 2 STEP RISERS
 APPROXIMATE 4 ? INCHES EACH. PLEASE SHOW THIS SAME
 CHANGE IN ELEVATION ON THE LIFE SAFETY PLAN A 1.00.
  
 4B) WITH THE CHANGE IN GRADE AT THE EAST SIDE OF THE
 BUILDING AND CLOSENESS TO THE CITY SIDEWALK PLEASE
 PROVIDE HOW COMPLIANCE WILL BE MET WITH SECTION 1003.5
 OF THE 2014 FBC-B OR EXCEPTION # 2?
  
 4C) DEPENDING ON THE OUTCOME OF COMMENT 4B) IF THE RAMP
 METHOD OF COMPLIANCE IS NOT USED THEN PLEASE PROVIDE
 COMPLIANCE WITH SECTION 216.4.3 DIRECTIONAL SIGNAGE OF
 WHERE THE ACCESSIBLE ENTRANCE IS LOCATED.
  
 5) SHEET C-1. FOR THE HANDICAPPED PARKING SPACE AND
 ACCESS AISLE PLEASE PROVIDE ELEVATION MARKERS AT THE
 FOUR CORNERS TO VERIFY COMPLIANCE WITH 2014
 ACCESSIBILITY CODE 502.4 AND EXCEPTION SLOPES NOT
 STEEPER THAN 1:48 SHALL BE PERMITTED.
  
 6) SHEETS A 4.00, A 4.01 & S1.4, NONE OF THESE SHEETS
 INDICATE THE SLOPE OF THE UPPER ROOF, WILL NEED THE
 SLOPE OF THE UPPER ROOF TO VERIFY PRESSURES ON THE
 UPPER ROOF, MEAN ROOF IS GIVEN, THANK YOU. 107.2.1.3
 ADDITIONAL INFORMATION REQUIRED TO VERIFY PRESSURES.
  
 7) SHEET S2.1 UPPER RIGHT CORNER OF THE SHEET, NOTES
 INDICATE THE USE OF 5/8 INCH PERFORMANCE RATED PLYWOOD.
 SHEET S3.3 NOTES 5 & 8 BOTH INDICATE THE USE OF 5/8
 INCH PLYWOOD. THE DESIGNER OF RECORD HAS DESIGNED THIS
 BUILDING TO BE CONSTRUCTION TYPE II-B. IN THE 2014
 FBC-B SECTION 603.1.1.1.3 FIRE RETARDANT TREATED WOOD
 SHALL BE PERMITTED IN ROOF CONSTRUCTION INCLUDING,
 GIRDERS, TRUSSES, FRAMING, AND DECKING. PLEASE CORRECT
 THE PLANS, TO FIRE RETARDANT TREATED WOOD.
  
 8) SHEET S2.1 THE BOTTOM TOWER (SOUTH) HAS A WALL
 SECTION DETAIL # 8/ S3.2, PLEASE CORRECT FOR A WALL
 SECTION. TYPO, 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 9A) SHEET A 5.01 DETAIL # 3 THE UPPER ROOF DETAIL
 INDICATES SHEATHING IS TO BE ATTACHED TO PRE-FABRICATED
 WOOD TRUSSES OR METAL ROOF TRUSSES REFER TO STRUCTURAL
 DRAWINGS. 2014 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.2.1.3: W.P.B. ADMINISTRATIVE CODE/2014 DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR
 IN PART, OR, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE
 USED AS A SUBSTITUTE FOR SPECIFIC INFORMATION".
  
 9B) SHEET S2.2 IN THE HIGH ROOF FRAMING PLAN THE
 TRUSSES ARE INDICATED TO BE PRE-MANUFACTURED WOOD
 TRUSSES. TYPE II-B. PLEASE UPDATE PLANS THAT THE
 TRUSSES HAVE TO BE FIRE RETARDANT TREATED TRUSSES. WE
 WILL ALSO NEED CONFIRMATION FOR THE TRUSS PLANT THEY
 WILL BUILD WOOD FIRE RETARDANT TREATED WOOD TRUSSES
 BECAUSE OF THE FIRE RETARDANT IMPREGNATED TREATMENT.
 THAT THE SALTS WILL NOT AFFECT THE TEETH IN THE TRUSS
 PANEL FASTENERS. IN THE 2014 FBC-B SECTION 603.1.1.1.3
 FIRE RETARDANT TREATED WOOD SHALL BE PERMITTED IN ROOF
 CONSTRUCTION INCLUDING, GIRDERS, TRUSSES, FRAMING, AND
 DECKING. PLEASE CORRECT THE PLANS, TO FIRE RETARDANT
 TREATED WOOD.
 10) SHEET S3.2 SHOWS DETAIL # 8 THE CURB DETAIL FOR RTU
 SUPPORT. THE DETAIL DOES SHOW THE ATTACHMENT OF THE
 CURB TO THE ROOF FRAMING MEMBERS AND A MAXIMUM CURB
 HEIGHT OF 14 INCHES FROM THE FINISH ROOF DECK TO THE
 TOP OF THE CURB, THE DETAIL DOES NOT SHOW THE OVERLAP
 OF THE TOP OF THE RTU CURB, AS DETAILED ON M3. THE
 BOTTOM OF THE RTU UNIT (OVERLAP) HAS TO BE MOUNTED ON
 CURBS RAISED A MINIMUM OF 8 INCHES (203 MM) ABOVE THE
 ROOF SURFACE, OR WHERE ROOFING MATERIALS EXTEND BENEATH
 THE UNIT. FBC-B 1509.6.5 MECHANICAL UNITS.
  
 11) SHEET M-3 ROOF TOP MOUNTING DETAIL SHOWS THE USE OF
 A HURRICANE STRAP BEING USED FOR ANCHORING OF THE RTU
 TO THE CURB. PLEASE PROVIDE THE MANUFACTURER OF THE
 STRAP DETAIL WHERE THIS IS AN APPROVED METHOD OF USE.
 IT APPEARS THE STRAP IS BEING BENT AT 90 DEGREE ANGLES.
 SPECIFY MANUFACTURER AND MODEL OF STRAP AND THE AMOUNT
 OF ANCHORS AND SIZE OF ANCHORS.
 FOR ALL ROOF TOP EQUIPMENT, CURBS DETAILED ATTACHMENT
 TO THE ROOF FRAMING & DECK AS WELL AS FROM THE CURB OR
 ROOF STAND TO THE EQUIPMENT ABOVE.
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 12) SHEET A 5.00 NOTE 25 INDICATES THE USE OF 5/8 INCH
 DENSEGLASS SHEATHING, PROVIDE A PRODUCT APPROVAL
 SHOWING THE TESTING AND TO WHAT DESIGN PRESSURES THE
 DENSEGLASS CAN BE INSTALLED. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 13) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, FLAT AND SLOPED
 ROOFING, CURBS, ROOF TOP VENTILATORS
  
 14) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 15A) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 15B) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 16) EFIS SYSTEMS: PLEASE PROVIDE THE PRODUCT APPROVAL
 FOR THE SYSTEM TO BE INSTALLED. PLEASE ALSO PROVIDE THE
 MANUFACTURERS INSTALLATION BROCHURE PROVIDING
 COMPLIANCE WITH 2014 FBC-B SECTIONS;
 1408.2 PERFORMANCE CHARACTERISTICS.
 1408.2 PERFORMANCE CHARACTERISTICS.
 1408.3 STRUCTURAL DESIGN.
 1408.4 WEATHER RESISTANCE.
 1408.4.1 EIFS WITH DRAINAGE.
 408.4.1.1 WATER-RESISTIVE BARRIER.
 1408.5 INSTALLATION.
  
 17) PLEASE NOTE SHEET A 7.01 SHOWS A 3 PLY ROOF SYSTEM
 AND THE USE OF RIGID INSULATION BOARD OVER CORRUGATED
 METAL DECKING. PLEASE SUPPLY THE INSULATION PRODUCT
 APPROVAL, DEPENDING ON THE TYPE OF INSULATION BOARD
 INSTALLED ADDITIONAL MANUFACTURERS SPECIFICATION WILL
 PROVIDE THE VARIOUS WAYS THE INSULATION BOARD CAN BE
 VENTILATED. NOTE THE DESIGNER OF RECORD HAS NOT
 SPECIFIED WHAT TYPE OF VENTING WILL BE REQUIRED FOR
 THIS PROJECT, NOR IS THERE ANY SPEC LISTED UNDER THE
 STEEL DECK S1.1.
 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND
 DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 VENTING, FASTENING REQUIREMENTS, FLASHING REQUIREMENTS
 AND WIND RESISTANCE RATING THAT ARE REQUIRED TO BE
 INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL
 INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR
 THE SPECIFIC SITE.
  
 18) FOR ALL ROOFING PRODUCTS (PRODUCT APPROVALS) PLEASE
 IDENTIFY ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED
 PRESSURES FOR ROOF ZONE # 1. REVIEW THE PRODUCT
 APPROVAL LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED
 FOR ROOF ZONES 2 & 3. FASTENER DENSITIES SHALL BE
 INCREASED FOR BOTH INSULATION & THE BASE SHEET AS
 CALCULATED IN COMPLIANCE WITH ROOFING APPLICATION
 STANDARDS RAS 117. CALCULATION PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
 19) PLEASE PROVIDE THE PRODUCT APPROVAL AND
 INSTALLATION INSTRUCTIONS FOR THE ROOF TOP LADDER. 2014
 FBC-B 1509.6.4 EQUIPMENT AND APPLIANCES ON ROOFS OR
 ELEVATED STRUCTURES.
  
 20) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 21) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  