| 2017-05-12 14:12:24 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET 1 - THERE IS NO INDICATION REVIEW AND/OR |
| | COMPLOIANCE WITH ANY FIRE CODE. |
| | |
| | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| | 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING |
| | THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| | APPLICABLE CODES OR STANDARDS. |
| | |
| | PLEASE PROVIDE AN APPLICABLE NOTE AND ENSURE |
| | COMPLIANCE. |
| | |
| | |
| | |
| | |
| | 2) SHEET 1 - THERE IS NO OCCUPANCY CLASSIFICATION PER |
| | THE FLORIDA FIRE PREVENTION CODE AND NFPA 101. |
| | |
| | CHAPTER 6 CLASSIFICATION OF OCCUPANCY AND |
| | HAZARD OF CONTENTS |
| | 6.1 CLASSIFICATION OF OCCUPANCY. |
| | 6.1.1 GENERAL. |
| | 6.1.1.1 OCCUPANCY CLASSIFICATION. THE OCCUPANCY OF A |
| | BUILDING OR STRUCTURE, OR PORTION OF A BUILDING OR |
| | STRUCTURE, SHALL BE CLASSIFIED IN ACCORDANCE WITH 6.1.2 |
| | THROUGH 6.1.13. OCCUPANCY CLASSIFICATION SHALL BE |
| | SUBJECT TO THE RULING OF THE AUTHORITY |
| | HAVINGJURISDICTION WHERE THERE IS A QUESTION OF PROPER |
| | CLASSIFICATION IN ANY INDIVIDUAL CASE. |
| | |
| | A DISPLAY AREA IS INDICATED; IS THIS MERCANTILE? |
| | |
| | PLEASE PROVIDE A NARRATIVE OF THE PROPOSED USE OF THE |
| | OCCUPANCY AND A NOTE INDICATING THE APPLICBALE |
| | OCCUPANCY CLASSIFICATION AND ENSURE COMPLIANCE WITH |
| | THAT OCCUPANCY. |
| | |
| | |
| | 3) SHEET 1 - THERE IS NO PROPOSED OCCUPACNY LOAD. |
| | |
| | PER NFPA 101 - |
| | |
| | 7.3 CAPACITY OF MEANS OF EGRESS. |
| | 7.3.1 OCCUPANT LOAD. |
| | 7.3.1.1 SUFFICIENT CAPACITY. |
| | 7.3.1.1.1 THE TOTAL CAPACITY OF THE MEANS OF EGRESS FOR |
| | ANY STORY, BALCONY, TIER, OR OTHER OCCUPIED SPACE SHALL |
| | BE SUFFICIENT FOR THE OCCUPANT LOAD THEREOF. |
| | |
| | 7.3.1.2* OCCUPANT LOAD FACTOR. THE OCCUPANT LOAD IN ANY |
| | BUILDING OR PORTION THEREOF SHALL BE NOT LESS THAN THE |
| | NUMBER OF PERSONS DETERMINED BY DIVIDING THE FLOOR AREA |
| | ASSIGNED TO THAT USE BY THE OCCUPANT LOAD FACTOR FOR |
| | THAT USE AS SPECIFIED IN TABLE 7.3.1.2, FIGURE |
| | 7.3.1.2(A), AND FIGURE 7.3.1.2(B). WHERE BOTH GROSS AND |
| | NET AREA FIGURES ARE GIVEN FOR THE SAME OCCUPANCY, |
| | CALCULATIONS SHALL BE MADE BY APPLYING THE GROSS AREA |
| | FIGURE TO THE GROSS AREA OF THE PORTION OF THE BUILDING |
| | DEVOTED TO THE USE FOR WHICH THE GROSS AREA FIGURE IS |
| | SPECIFIED AND BY APPLYING THE NET AREA FIGURE TO THE |
| | NET AREA OF THE PORTION OF THE BUILDING DEVOTED TO THE |
| | USE FOR WHICH THE NET AREA FIGURE IS SPECIFIED. |
| | |
| | PLEASE PROVIDE A NOTE INDICATING THE PROPOSED OCCUPANCY |
| | LOAD CALCULATION. |
| | |
| | |
| | |
| | 4) SHEET 1 & 2 - THERE IS NO REFERNCE TO THE FRONT OF |
| | THE BUILDING AND/OR NORTH INDICATIONS. |
| | |
| | PLEASE PROVIDE A NOTE TO NORTH AND/OR IDENTIFY WHERE N |
| | DIXIE HIGHWAY IS LOCATED IN REFERNCE TO THE BUILDING. |
| | |
| | |
| | |
| | |
| | 5) SHEET 1 - THERE ARE TWO EXITS INDICATING PASSAGE |
| | THROUGH A STORAGE AREA. PER NFPA 101, CHAPTER 7. |
| | |
| | 7.5.1.6 EXIT ACCESS FROM ROOMS OR SPACES SHALL BE |
| | PERMITTED TO BE THROUGH ADJOINING OR INTERVENING ROOMS |
| | OR AREAS, PROVIDED THAT SUCH ROOMS OR AREAS ARE |
| | ACCESSORY TO THE AREA SERVED. FOYERS, LOBBIES, AND |
| | RECEPTION ROOMS CONSTRUCTED AS REQUIRED FOR CORRIDORS |
| | SHALL NOT BE CONSTRUED AS INTERVENING ROOMS. EXIT |
| | ACCESS SHALL BE ARRANGED SO THAT IT IS NOT NECESSARY TO |
| | PASS THROUGH ANY AREA IDENTIFIED UNDER PROTECTION FROM |
| | HAZARDS IN CHAPTERS 11 THROUGH 43. |
| | |
| | IF THIS IS AN EXISTING BUSINESS OCCUPANCY - |
| | |
| | 38.3.2 PROTECTION FROM HAZARDS. |
| | 38.3.2.1* GENERAL. HAZARDOUS AREAS INCLUDING, BUT NOT |
| | LIMITED TO, AREAS USED FOR GENERAL STORAGE, BOILER OR |
| | FURNACE ROOMS, AND MAINTENANCE SHOPS THAT INCLUDE |
| | WOODWORKING AND PAINTING AREAS SHALL BE PROTECTED IN |
| | ACCORDANCE WITH SECTION 8.7. |
| | |
| | A NOTE IS INDICATING STORAGE OF FILE CABINETS. THIS |
| | SPACE CAN NOT BE USED FOR GENERAL STORAGE AND THE PATH |
| | OF TRAVEL SHALL ALWAYS BE MAINTAINED. |
| | |
| | PLEASE PROVIDE A CABINET FILE FLOOR PLAN THAT INDICATES |
| | THE REQUIRED EXIT PATH CLEARANCE EVEN WHEN OPENED. |
| | |
| | |
| | |
| | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |