| Plan Review Notes For Permit 17050393 |
| Permit Number |
17050393 |
|
| Review Stop |
R |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-03-06 16:49:17 | 1- PROVIDE PRODUCT APPROVAL (TWO COPIES) AS REQUIRED BY | | | FAC 61G20-3.001 FOR: | | | A) FLAT ROOF. ONLY THE COVER PAGE OF NOA 17-0824.11 WAS | | | SUBMITTED. PROVIDE COMPLETE PRODUCT APPROVAL AND, | | | CLEARLY MARK WHICH APPROVED ASSEMBLY FROM THE PRODUCT | | | APPROVAL SUBMITTED IS GOING TO BE INSTALLED TO VERIFY | | | COMPLIANCE WITH THE DESIGN PRESSURES. IF THE SELECTED | | | ASSEMBLY DON'T MEET THE DESIGN PRESSURES FOR ALL ROOF | | | ZONES, THEN SIGNED AND SEALED RAS 117 CALCULATIONS WILL | | | BE REQUIRED. | | | |
|