| 2018-03-06 17:10:01 | RESIDENTIAL (R3) ADDITION, SECOND MECHANICAL REVIEW |
| | CHECKLIST. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | 1- THERE ARE NO CITY RECORDS SHOWING ANY A/C WORK IN |
| | THIS HOUSE. PROVIDE COMPLETE A/C PLANS SHOWING ALL THE |
| | EQUIPMENT AND DUCTWORK. SPECIFY THE EQUIPMENT |
| | MANUFACTURER AND MODEL. COORDINATE INFORMATION WITH |
| | EQUIPMENT SIZING CALCULATIONS. SEE ITEM #2 BELOW. |
| | SEC. 107.3.5.3(10) CITY AMENDMENTS. |
| | |
| | RESPONSE: MECHANICAL PLAN DRAWING M-1 SUBMITTED ONLY |
| | PROVIDES INFORMATION FOR THE ADDITION. THERE ARE NO |
| | PERMITS FOR THE A/C UNIT. PROVIDE ALL THE INFORMATION |
| | REQUESTED ABOVE. |
| | |
| | 2- PROVIDE EQUIPMENT SIZING CALCULATIONS AS REQUIRED BY |
| | SEC. R403.6.1 FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | |
| | RESPONSE: CALCULATIONS SUBMITTED ARE ONLY FOR THE |
| | ADDITION. NEED TO PROVIDE COMPLETE EQUIPMENT SIZING |
| | CALCULATIONS FOR ENTIRE HOUSE SINCE THERE ARE NO |
| | PERMITS FOR THE A/C EQUIPMENT. PROVIDE COMPLETE |
| | INFORMATION FOR THE EQUIPMENT AS REQUIRED BY SEC. |
| | R403.6 FBC-ENERGY CONSERVATION. NOTE: COORDINATE |
| | INFORMATION WITH THE ENERGY CALCULATIONS. IT LOOKS LIKE |
| | THE WINDOW INFORMATION DOESN'T MATCH INFORMATION SHOWN |
| | ON THE ENERGY CALCULATIONS. |
| | |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWING. DON"T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS |
| | FOR REFERENCE. |
| | |