| 2018-03-05 16:51:57 | ADDITION, SECOND BUILDING REVIEW CHECKLIST. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| | COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT. |
| | BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID |
| | RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF |
| | THE UNIFIED LAND DEVELOPMENT CODE. |
| | NOTE: THIS CAN BE DONE LATER WHEN THE PLANS ARE |
| | APPROVED AND PERMIT CARD IS READY TO BE PROCESSED. |
| | |
| | 2- ENERGY CALCULATIONS SUBMITTED: |
| | A) OWNER TO SIGN THE ENERGY CALCULATIONS AS REQUIRED BY |
| | SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2017). |
| | |
| | B) DUCT WORK INSULATION R-VALUE IN ITEM #11(A) NEEDS TO |
| | BE REVISED. ACCORDING TO TABLE R402A NEED R-8 |
| | INSULATION FOR DUCTWORK LOCATED IN THE ATTIC. SEC. |
| | R101.5.1.1.1 FBC-ENERGY CONSERVATION. |
| | |
| | C) ITEM # 11(B) INDICATES THAT THE AHU LOCATION IS THE |
| | GARAGE. THERE IS NOT GARAGE IN THIS HOUSE. SEE PLANS |
| | AND REVISE AS REQUIRED. SEC. R101.5.1.1.1 FBC-ENERGY |
| | CONSERVATION. NOTE: COORDINATE WITH A/C PLANS. SEE |
| | MECHANICAL COMMENTS. |
| | |
| | D) NEED TO COMPLETE THE TABLE R402B AS REQUIRED BY |
| | GENERAL INSTRUCTIONS NOTE #3 ON THE FRONT PAGE OF FORM |
| | R402-2014 SUBMITTED. COMPLETE TABLE R402B AS REQUIRED. |
| | SEC. R101.5.1.1.1 FBC-ENERGY CONSERVATION. |
| | |
| | E) COMPLETE INFORMATION ON TOP OF FORM. NEED THE |
| | OWNER'S NAME AND BUILDER'S NAME. SEC. R101.5.1.1.1 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | 3- VALUATION WAS UPDATED TO $12,544 AS REQUIRED BY SEC. |
| | 109.3 CITY AMENDMENTS. THE PERMIT FEE BALANCE DUE IS |
| | $130.91. |
| | |
| | 4-WALL SECTION ON SHEET 02: |
| | SPECIFIED LOCATION OF ROOF VENTS DON'T PROVIDE CROSS |
| | VENTILATION AS REQUIRED BY SEC. R806.1 FBC-RESIDENTIAL. |
| | VENTS LOCATED AT 6'-0" O.C. DON'T PROVIDE VENTILATION |
| | TO THE 2X12 ROOF JOISTS THAT ARE BETWEEN VENTS. |
| | REMEMBER THAT ROOF FRAMING MEMBERS ARE 2X12 SOLID |
| | JOISTS NOT ENGINEERED TRUSSES. THERE IS NOT CROSS |
| | VENTILATION. REVISE AS REQUIRED. |
| | |
| | 5- PROVIDE PRODUCT APPROVAL (TWO COPIES) AS REQUIRED BY |
| | FAC 61G20-3.001 FOR: |
| | A) FLAT ROOF. ONLY THE COVER PAGE OF NOA 17-0824.11 WAS |
| | SUBMITTED. PROVIDE COMPLETE PRODUCT APPROVAL AND, |
| | CLEARLY MARK WHICH APPROVED ASSEMBLY FROM THE PRODUCT |
| | APPROVAL SUBMITTED IS GOING TO BE INSTALLED TO VERIFY |
| | COMPLIANCE WITH THE DESIGN PRESSURES. IF THE SELECTED |
| | ASSEMBLY DON'T MEET THE DESIGN PRESSURES FOR ALL ROOF |
| | ZONES, THEN SIGNED AND SEALED RAS 117 CALCULATIONS WILL |
| | BE REQUIRED. |
| | |
| | B) SINGLE HUNG WINDOWS: ONLY THE COVER PAGE OF NOA |
| | 15-0602.06 WAS SUBMITTED. PROVIDE COMPLETE PRODUCT |
| | APPROVAL. |
| | |
| | C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS |
| | AND DETAILS. REPEAT COMMENT. NOT ADDRESSED AT ALL. |
| | NOTE: PROVIDE FLORIDA PRODUCT APPROVAL COVER PAGE AND |
| | ONLY THE PAGE SHOWING THE SPECIFIED CONNECTOR OR DESIGN |
| | PROFESSIONAL TO LIST THE FLORIDA PRODUCT APPROVAL |
| | NUMBER NEXT TO EACH SPECIFIED CONNECTOR. |
| | |
| | D) PRECAST LINTELS SPECIFIED ON PLANS. REPEAT COMMENT. |
| | NOT ADDRESSED AT ALL. |
| | |
| | 6- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWING. DON"T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS |
| | FOR REFERENCE. |
| | |