| 2017-06-06 17:50:15 | RESIDENTIAL (R3) ADDITION, MECHANICAL REVIEW COMMENTS. | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- SCOPE OF WORK ON SHEET 01 SPECIFIES "ADD REAR A/C | | | ADDITION W/BATH". THERE IS NO INFORMATION SUBMITTED | | | SHOWING HOW THE PROPOSED ADDITION IS GOING TO HAVE | | | CONDITIONED AIR. NOTE: THERE ARE NO CITY RECORDS | | | SHOWING ANY A/C WORK IN THIS HOUSE. PROVIDE COMPLETE | | | A/C PLANS SHOWING ALL THE EQUIPMENT AND DUCTWORK. | | | SPECIFY THE EQUIPMENT MANUFACTURER AND MODEL. | | | SEC. 107.3.5.3(10) CITY AMENDMENTS. | | | | | | 2- PROVIDE EQUIPMENT SIZING CALCULATIONS AS REQUIRED BY | | | SEC. R403.6.1 FBC-ENERGY CONSERVATION, 5TH EDITION | | | (2014). | | | | | | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | | COMMENT TO EXPEDITE THE REVIEW PROCESS. | | | ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD | | | DRAWING. DON"T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS | | | FOR REFERENCE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | | | | |
|